2007-06-26 15:38:25BUILDING PLAN REVIEW
 PERMIT: 07020482
 ADD: 1501 PRESIDENTIAL WAY
 CONT: GRUBER HALL CORP
 TEL: (561)666-3377
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A-1 DOES NOT INDICATE THE MINIMUM BUILDING
 TYPE. THE LIST BELOW IS REQUIRED TO BE ON THE PLAN,
 110.2 FBC CODE, INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 THE PLANS ARE NOT CONSISTANT THE GENERAL INFO LISTING
 THE ABOVE REQUIEMENTS STATES THIS IS A TYPE VB BUILDING
 (NOTE C) , NOTE E INDICATES FIRE SPRINKLERS ARE PRESENT
 AND AREA INCREASES WERE TAKEN.
 THIS IS WHERE THERE IS A DISCREPANCY AT THE BOTTOM LEFT
 OF SHEET A1 GENERAL SPECS NOTE 21THIS NOTE INDICATES
 "NO FRONTAGE OR FIRE SPRINKLER INCREASES MADE".
 THE DESIGNER OF RECORD NEEDS TO MAKE CORRECTIONS TO THE
 PLAN, THE LETTER SIZE REPONSE CAN NOT BE PART OF THE
 LEGAL DOCUMENTS SINCE IT IS NOT SIGNED NOR SEALED.
  
 COMMENT # 3FROM THE 2ND REVIEW: FROM THE PREVIOUS
 REVIEW:SHEET A-1 PLANS INDICATED THIS IS A TYPE II
 BUILDING,? THIS IS TO BE A MINIMUM BUILDING TYPE! THE
 PLAN NOW INDICATE IT TO BE A TYPE V CONSTRUCTION.
 THE PLANS ALSO STATE THAT THE TOTAL SQUAREFOOTAGE
 FORTHE BUILDING TO BE 24,963 SQUARE FEET WHICH IS OVER
 THE LIMIT OF 9,000 SQUARE FEET FOR A TYPE VB BUILDING.
 FURTHER IN THE REVIEW I MENTIONED THAT IF THERE WERE
 FIRE SPINKLERS INCREASES COULD BE TAKEN , AND THE
 RESPONSE WAS THERE WERE NONE. I ALSO INDICATED THAT
 FRONTAGE INCREASES COULD BE TAKEN, NONE WERE TAKEN. IF
 THE FRONTAGE INCREASES WERE TAKEN I BELIEVE THE FIGURES
 WOULD DECLARE FOR A MINIUM BUILDING TYPE THIS WOULD BE
 A TYPE III-B BUILDING. PLEASE CORRECT THE MINIUM
 BUILDING TYPE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  