Plan Review Notes
Plan Review Notes For Permit 07020482
Permit Number 07020482
Review Stop P
Sequence Number 2
Notes
Date Text
2007-05-30 11:25:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 ****FROM PREVIOUS REVIEW:
  
  
 1. SUBMIT A DETAIL FOR THE NEW TOILET ROOMS, (TOILET
 ROOMS 2 & 4). SHOW COMPLIANCE FOR THE FOLLOWING: FOR
 W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE - NOT ADDRESSED, NO
 RESPONSE
 B. 11-4.16.3 HEIGHT - NOT ADDRESSED, NO RESPONSEC.
 11-4.16.4 GRAB BARS - NO GRAB BAR BEHIND THE WATER
 CLOSET INDICATED.
 D. 11-4.16.5 FLUSH CONTROLS - NOT ADDRESSED, NO
 RESPONSE
 E. 11-4.16.6- OK
 FOR THE LAVS:
 A. 11-4.19.2- OK
 B. 11-4.19.3- OK
 C. 11-4.19.4 EXPOSED PIPES & SURFACES - NOT ADDRESSED,
 NO RESPONSE
 D. 11-4.19.5 FAUCETS - NOT ADDRESSED, NO RESPONSEE.
 11-4.19.6- OK
 FOR THE TOILET ROOMS:
 A.- OK
  
 2. SUBMIT A DETAIL FOR THE BREAK ROOM SINK. SHOW
 COMPLIANCE FOR THE FOLLOWING:
 A. 11-4.24.2- OK
 B. 11-4.24.3 KNEE CLEARANCE- NOT ADDRESSED, NO
 RESPONSE
 C. 11-4.24.4- OK
 D. 11-4.24.5- OK
 E. 11-4.24.6 EXPOSED PIPES & SURFACES- NOT
 ADDRESSED, NO RESPONSE
 F. 11-4.24.7 FAUCETS- NOT ADDRESSED, NO RESPONSE
  
 3. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES,& IF QUICK CLOSING VALVES ARE INSTALLED, WATER
 HAMMER ARRESTORS PER SECTION 604.9, LOCATED NEAR THE
 FIXTURE, IN AN "EFFECTIVE RAGE", (NOT IN THE CEILING),
 PER PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 SECTION 106.3.5.1.3(3)(10)(13).
 ****RESPONSE NOTED, BUT A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE SUPPLY LINE TO THE ICE MAKER IN THE
 REFRIG.--WATER RISER DIAGRAM FOR EXAM ROOM #1 AND
 TOILET ROOM #2 MISLABELED.--THE SINK IN EXAM ROOM
 #4 IS NOT SHOWN ON THE RISER DIAGRAM.
  
 4. A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1.
 ****RESPONSE NOTED, BUT A DRINKING FOUNTAIN IS REQUIRED
 PER TABLE 403.1 AND A BOTTLED WATER COOLER CAN NOT BE
 SUBSTITUTED FOR MORE THAN 50% OF THE REQUIRED DRINKING
 FOUNTAINS. IF ONE IS REQUIRED, THEN IT SHALL BE A
 DRINKING FOUNTAIN.
  
 5. OK
 6. OK
  
 ************NEW COMMENTS************
  
 1B. A TURNING AREA IS REQUIRED IN THE ACCESSIBLE TOILET
 ROOMS. SECTION 11-4.22.3.
  
 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 533.80(2)(B). THIS IS GIVEN AS A
 ONE TIME NOTICE AS SOME OF THE COMMENTS ARE THE SAME AS
 THE PREVIOUS REVIEW.
  
 3. TWO COMPLETE SETS OF PLANS SHALL BE SUBMITTED.
 PLEASE ADD ALL SHEETS FROM THE FIRST REVIEW THAT WILL
 NOT BE CHANGED TO THE NEW SHEETS FROM THE SECOND
 REVIEW. (SEE D-1). SECTION 106.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL KSTEVENS@
 WPB.ORG


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved