Plan Review Notes
Plan Review Notes For Permit 07020482
Permit Number 07020482
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-05-07 15:43:03*****DENIED*****
  
 WITH THE EXCEPTION OF #1, THE FOLLOWING COMMENTS TAKEN
 FROM THE PREVIOUS FIRE PLAN REVIEW STILL NEED TO BE
 ADDRESSED:
  
  
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.IF THE BUILDING OR PORTIONS OF THE BUILDING ARE TO
 BE OCCUPIED DURING THE INTERIOR RENOVATION, THIS SHALL
 BE PERMITTED ONLY WHERE THE REQUIRED MEANS OF EGRESS
 AND REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND
 CONTINUOUSLY MAINTAINED.
  
 6.PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATIONS FOR THE NEW CEILING TILES IN TERMS OF
 CLASS A, CLASS B, OR CLASS C.
  
 7.WILL THE REMOVAL AND/OR RELOCATION OF SOME OF THE
 INTERIOR PARTITIONS IMPACT THE FIRE SPRINKLER HEADS? IF
 SO, SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER REMODEL.
  
 8.SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) IN
 THIS OFFICE SPACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW