| 2007-04-24 17:32:25 | ** UNSAT2ND REVIEW** |
| | |
| | ** PLEASE SEE THERE ARE NOTES FROM THE PREVIOUS REVIEW |
| | WHICH STILL NEED TO BE ADDRESSED ALONG WITH TWO NEW |
| | NOTES. |
| | |
| | |
| | 1) NOTE: THIS IS THE SAME COMMENT. PLEASE KNOW THAT |
| | STATING THE LATEST ADOPTED EDITION ETC IS NOT |
| | PERMITTED. |
| | PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED |
| | CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| | 8TH, 2006. |
| | 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS |
| | SUBMITTED |
| | 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED. |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE |
| | STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED |
| | IN THIS REVIEWER(S) COMMENTS. |
| | |
| | 2) NOTE: PLEASE CLARIFY THE GROUNDING ETC AND USE OF |
| | ANY OF THESE ITEMS FOR ANY STORAGE OR PROCEDURES. THIS |
| | MAY ELABORATED IN NOTES, UNLESS SOME OF THESE ITEMS ARE |
| | INDEED IN USE, THEN ELECTRICAL PLANS WILL NEED TO BE |
| | ADJUSTED TO SHOWCLASS/ AND DIVISION LOCATIONS WHERE |
| | APPLICABLE. |
| | PLEASE 517.12, 517.13, 517.60, 517.62 AND OTHER PARTS |
| | OF 517. PLEASE SPECIFY AREAS AND USE IN THESE AREAS. |
| | PLEASE SPECIFY ANY USE OF ANESTHETIZING LOCATIONS IF |
| | THIS APPLIES TO THIS OFFICE AND USE. PLEASE BE SURE TO |
| | PLACE NOTES FOR TYPE OF WIRING METHODS AND GROUNDING AS |
| | REQUIRED PER SECTIONS STATED. |
| | |
| | 3) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND ALL |
| | CIRCUITING ON PLANS. PLEASE SEE THE COMPLETED PANEL |
| | SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE ARE |
| | SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. PLEASE |
| | SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. *SECTION |
| | 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE |
| | IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION. |
| | |
| | 4) NOTE:PLEASE SEE 700.12E FOR EMERGENCY AND EXIT |
| | LIGHTS. PLEASE SEE HALLWAY EMERGENCY/EXIT LIGHT WHICH |
| | IS CIRCUITED TO OFFICE #1 AND NOT HALL. |
| | THESE ARE REQUIRED TO BE CIRCUITED TO LOCAL LIGHTING |
| | BRANCH CIRCUIT. |
| | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | 5) NOTE: PLEASE SEE PLEASE SHOW PER, 220.14,220.44 WHEN |
| | A RECEPTACLE LOAD IS KNOWN, THE HIGHER OF THE TWO SHALL |
| | BE SHOWN.. |
| | |
| | 6) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| | CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, |
| | .1.2 AND .1.3 FOR NEW INSTALLATIONS AS REQUIRED PER |
| | 13.101 |
| | PLEASE SEE BY DEFINITION THIS SPACE IS IN A BUILDING |
| | GREATER THAN 5K SQ FT. |
| | PLEASE SHOW COMPLIANCE WITH THIS AND IF THERE ARE ANY |
| | QUESTIONS, PLEASE CALL TO GO OVER THIS. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE SHOWN |
| | AS A METHOD D? PLEASE SEE 13-415.1.AB.1.1,13-415.1.A, |
| | 13-415.1.B, 13-415.1.C, 13-415.2 FOR LIGHTING |
| | PERFORMANCE CALCULATIONS. |
| | PLEASE ALSO SEE THE SHEETS SUBMITTED CONTAIN HAND DRAWN |
| | ITEMS AND WHITE OUT ON SHEETS WHICH ARE SIGNED, DATED |
| | AND SEALED BY AN ARCHITECT WHICH IS NOT PERMITTED. FS |
| | 481.221 |
| | PLEASE CALL TO GO OVER THESE REQUIREMENTS FROM FBC |
| | CHAPTER 13, 2004 FBC W/ THE 2006 REVISIONS. |
| | |
| | PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC |
| | FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE |
| | LPD/CALCULATIONS IS REVIEWED FOR COMPLIANCE. |
| | PLEASE BE SURE TO INDICATE THE TYPE OF FIXTURE, WATTAGE |
| | AND NUMBER OF LAMPS PER FIXTURE. |
| | |
| | 7) NOTE: PLEASE SEE THE ELECTRICAL CLOSET WHERE |
| | ELECTRICAL PANEL AND EQUIPMENT IS SHOWN DOES NOT MEET |
| | 110.26 FOR MINIMUM CLEARANCES. PLEASE ALSO SEE PLANS |
| | APPEAR TO SHOW A SHELF ABOVE THE ELECTRICAL PANEL(S) |
| | AND EQUIPMENT. |
| | PLEASE SEE THERE ARE SEVERAL LIFE SAFETY AND FIRE |
| | HAZARDS WHICH ARE PRESENT. |
| | PLEASE SEE 110.26, 422.17, 408.7, 240.24. |
| | PLEASE RELOCATED OR ADJUST WALLS/DOORS/OPENINGS AND |
| | REMOVAL OF SHELVING. |
| | |
| | 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME AS SOME OF THE SAME COMMENTS |
| | ARE REPEATED FROM PREVIOUS REVIEW. |
| | ** AS STATED IN PREVIOUS REVIEW, PLEASE CALL TO GO OVER |
| | COMMENTS. THIS WILL HELP TO AVOID DELAYS ETC WITH |
| | PROJECT. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |