Plan Review Notes
Plan Review Notes For Permit 07020482
Permit Number 07020482
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-24 17:32:25** UNSAT2ND REVIEW**
  
 ** PLEASE SEE THERE ARE NOTES FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH TWO NEW
 NOTES.
  
  
 1) NOTE: THIS IS THE SAME COMMENT. PLEASE KNOW THAT
 STATING THE LATEST ADOPTED EDITION ETC IS NOT
 PERMITTED.
 PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED
 CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS
 SUBMITTED
 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE
 STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED
 IN THIS REVIEWER(S) COMMENTS.
  
 2) NOTE: PLEASE CLARIFY THE GROUNDING ETC AND USE OF
 ANY OF THESE ITEMS FOR ANY STORAGE OR PROCEDURES. THIS
 MAY ELABORATED IN NOTES, UNLESS SOME OF THESE ITEMS ARE
 INDEED IN USE, THEN ELECTRICAL PLANS WILL NEED TO BE
 ADJUSTED TO SHOWCLASS/ AND DIVISION LOCATIONS WHERE
 APPLICABLE.
 PLEASE 517.12, 517.13, 517.60, 517.62 AND OTHER PARTS
 OF 517. PLEASE SPECIFY AREAS AND USE IN THESE AREAS.
 PLEASE SPECIFY ANY USE OF ANESTHETIZING LOCATIONS IF
 THIS APPLIES TO THIS OFFICE AND USE. PLEASE BE SURE TO
 PLACE NOTES FOR TYPE OF WIRING METHODS AND GROUNDING AS
 REQUIRED PER SECTIONS STATED.
  
 3) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND ALL
 CIRCUITING ON PLANS. PLEASE SEE THE COMPLETED PANEL
 SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE ARE
 SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. PLEASE
 SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. *SECTION
 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE
 IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 4) NOTE:PLEASE SEE 700.12E FOR EMERGENCY AND EXIT
 LIGHTS. PLEASE SEE HALLWAY EMERGENCY/EXIT LIGHT WHICH
 IS CIRCUITED TO OFFICE #1 AND NOT HALL.
 THESE ARE REQUIRED TO BE CIRCUITED TO LOCAL LIGHTING
 BRANCH CIRCUIT.
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 5) NOTE: PLEASE SEE PLEASE SHOW PER, 220.14,220.44 WHEN
 A RECEPTACLE LOAD IS KNOWN, THE HIGHER OF THE TWO SHALL
 BE SHOWN..
  
 6) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1,
 .1.2 AND .1.3 FOR NEW INSTALLATIONS AS REQUIRED PER
 13.101
 PLEASE SEE BY DEFINITION THIS SPACE IS IN A BUILDING
 GREATER THAN 5K SQ FT.
 PLEASE SHOW COMPLIANCE WITH THIS AND IF THERE ARE ANY
 QUESTIONS, PLEASE CALL TO GO OVER THIS.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE SHOWN
 AS A METHOD D? PLEASE SEE 13-415.1.AB.1.1,13-415.1.A,
 13-415.1.B, 13-415.1.C, 13-415.2 FOR LIGHTING
 PERFORMANCE CALCULATIONS.
 PLEASE ALSO SEE THE SHEETS SUBMITTED CONTAIN HAND DRAWN
 ITEMS AND WHITE OUT ON SHEETS WHICH ARE SIGNED, DATED
 AND SEALED BY AN ARCHITECT WHICH IS NOT PERMITTED. FS
 481.221
 PLEASE CALL TO GO OVER THESE REQUIREMENTS FROM FBC
 CHAPTER 13, 2004 FBC W/ THE 2006 REVISIONS.
  
 PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC
 FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE
 LPD/CALCULATIONS IS REVIEWED FOR COMPLIANCE.
 PLEASE BE SURE TO INDICATE THE TYPE OF FIXTURE, WATTAGE
 AND NUMBER OF LAMPS PER FIXTURE.
  
 7) NOTE: PLEASE SEE THE ELECTRICAL CLOSET WHERE
 ELECTRICAL PANEL AND EQUIPMENT IS SHOWN DOES NOT MEET
 110.26 FOR MINIMUM CLEARANCES. PLEASE ALSO SEE PLANS
 APPEAR TO SHOW A SHELF ABOVE THE ELECTRICAL PANEL(S)
 AND EQUIPMENT.
 PLEASE SEE THERE ARE SEVERAL LIFE SAFETY AND FIRE
 HAZARDS WHICH ARE PRESENT.
 PLEASE SEE 110.26, 422.17, 408.7, 240.24.
 PLEASE RELOCATED OR ADJUST WALLS/DOORS/OPENINGS AND
 REMOVAL OF SHELVING.
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME AS SOME OF THE SAME COMMENTS
 ARE REPEATED FROM PREVIOUS REVIEW.
 ** AS STATED IN PREVIOUS REVIEW, PLEASE CALL TO GO OVER
 COMMENTS. THIS WILL HELP TO AVOID DELAYS ETC WITH
 PROJECT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]