| 2007-03-14 12:31:31 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | |
| | |
| | 1. SUBMIT A DETAIL FOR THE NEW TOILET ROOMS, (TOILET |
| | ROOMS 2 & 4). SHOW COMPLIANCE FOR THE FOLLOWING: FOR |
| | W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.4 GRAB BARS |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | E. 11-4.16.6 DISPENSERS |
| | FOR THE LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | E. 11-4.19.6 MIRRORS |
| | FOR THE TOILET ROOMS: |
| | A. THE DOORS SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE REQUIRED FOR ANY FIXTURE. SECTION 11-4.22.2. |
| | |
| | 2. SUBMIT A DETAIL FOR THE BREAK ROOM SINK. SHOW |
| | COMPLIANCE FOR THE FOLLOWING: |
| | A. 11-4.24.2 HEIGHT |
| | B. 11-4.24.3 KNEE CLEARANCE |
| | C. 11-4.24.4 SINK DEPTH |
| | D. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH |
| | REQUIRED. - NO CABINET DOORS ALLOWED |
| | E. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | F. 11-4.24.7 FAUCETS |
| | |
| | 3. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, |
| | VALVES,& IF QUICK CLOSING VALVES ARE INSTALLED, WATER |
| | HAMMER ARRESTORS PER SECTION 604.9, LOCATED NEAR THE |
| | FIXTURE, IN AN "EFFECTIVE RAGE", (NOT IN THE CEILING), |
| | PER PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| | SECTION 106.3.5.1.3(3)(10)(13). |
| | |
| | 4. A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1. |
| | |
| | 5. SHT A-1 ROOM FINISH SCHEDULE INDICATES DRYWALL FOR |
| | THE WALLS IN THE TOILET ROOMS.PER SECTION 1210.2, |
| | WALLS WITHIN 2FT OF URINALS AND WATER CLOSETS SHALL |
| | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT |
| | OF 4' ABOVE THE FLOOR. DRYWALL DOES NOT MEET THESE |
| | REQUIREMENTS. PLEASE INDICATE HOW THIS REQUIREMENT WILL |
| | BE ADDRESSED. |
| | |
| | 6. SHT A-1 THE PLUMBING RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS.-- |
| | THE SINK IN EXAM ROOM #1 SHALL DISCHARGE DOWNSTREAM OF |
| | THE FIXTURES IN TOILET ROOM #2 PER SECTION 909.1.-- |
| | THE SINK IN EXAM ROOM #2 IS INDICATED AS EXISTING ON |
| | THE FLOOR PLAN, BUT INDICATED AS NEW ON THE SANT RISER |
| | DIAGRAM.--THE NEW BREAK ROOM SINK IS NOT INDICATED |
| | ON THE RISER DIAGRAM.--THE NEW TOILET ROOM #4 IS |
| | NOT INDICATED ON THE SANT RISER DIAGRAM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |