Plan Review Notes
Plan Review Notes For Permit 07020482
Permit Number 07020482
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-28 07:39:55** UNSAT **
  
 ** PLEASE SEE OF THERE IS A SUITE TO THIS UNIT, PLEASE
 STATE ON PLANS. THIS IS TO VERIFIED WITH OUR ADDRESSING
 REVIEWER.
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS
 SUBMITTED
 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE
 STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED
 IN THIS REVIEWER(S) COMMENTS.
  
 2) NOTE:PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULE(S).
 PLEASE SEE THERE ARE A FEW ITEMS ON PLANS WHICH STILL
 DO NOT SHOW THE CIRCUITING.
 PLEASE SEE ALL CIRCUITS WHICH REFLECT TO A PANEL AND
 CIRCUITS WHICH ARE NOT PART OF THE SUBMITTED PANEL
 SCHEDULES SUBMITTED.
 PLEASE ALSO SEE WATER FOUNTAIN HAS BEEN ADDED TO PLANS;
 HOWEVER PLANS DO NOT INDICATE ANY ELECTRICAL
 RECEPTACLES FOR THIS UNIT.
 PLEASE CORRELATE AND COORDINATE ALL.
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE 517.12, 517.13, 517.60, 517.62 AND
 OTHER PARTS OF 517. PLEASE SPECIFY AREAS AND USE IN
 THESE AREAS. PLEASE SPECIFY ANY USE OF ANESTHETIZING
 LOCATIONS IF THIS APPLIES TO THIS OFFICE AND USE.
 PLEASE BE SURE TO PLACE NOTES FOR TYPE OF WIRING
 METHODS AND GROUNDING AS REQUIRED PER SECTIONS STATED.
  
 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE
 PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE
 ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED.
 PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 5) PLEASE SEE 700.12E FOR EMERGENCY AND EXIT LIGHTS.
 PLEASE KNOW AS CIRCUITING IS NOT SHOWN AT THIS TIME,
 COMPLIANCE FOR THIS CAN NOT BE VERIFIED. THESE SHALL BE
 CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT.
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 6) NOTE: PLEASE SHOW LOAD CALCULATIONS, PLEASE SHOW
 PER, 220.12, 220.14, 220.42, 220.44 ETC.
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER
 215.3, AND 230.42
 PLEASE INDICATE THE SIZE OF WHAT IS BEING SHOWN FOR THE
 EXISTING PANEL AND LOAD ON PANEL ALONG WITH NEW LOADS.
  
 7) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1,
 .1.2 AND .1.3.
 PLEASE SEE BY DEFINITION THIS SPACE IS IN A BUILDING
 GREATER THAN 5K SQ FT.
 PLEASE SHOW COMPLIANCE WITH THIS AND IF THERE ARE ANY
 QUESTIONS, PLEASE CALL TO GO OVER THIS.
 PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC
 W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2
 FOR LIGHTING PERFORMANCE CALCULATIONS ALONG WITH ENERGY
 CALCULATIONS.
 PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC
 FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE
 LPD/CALCULATIONS IS REVIEWED FOR COMPLIANCE.
 * PLEASE KNOW AS THE COMPLETE SCOPE OF WORK SEEMS TO BE
 MORE THAN APPLIED FOR ON PERMIT APPLICATION, ENERGY
 CALCULATIONS MAY ALSO BE REQUIRED FOR SPECIFIC
 USE/AREA.
 PLEASE BE SURE TO HAVE THE DESIGNER OF RECORD FOR THE
 ENERGY CALCULATIONS SIGN, DATE AND SEAL THESE AS
 REQUIRED PER 13-103.1.1.1
 *PLEASE SEE NOTES ON PLANS MENTIONS SOME OF THESE AREAS
 AS EXISTING FOR NO WORK, YET PLANS INDICATE WORK BEING
 DONE IN THESE AREAS.
  
 8) NOTE: PLEASE SEE PLAN WHERE WHAT SEEMS TO BE A WATER
 HEATER IN THE EQUIPMENT CLOSET WITH A RECEPTACLE TO
 *PLUG-IN* THIS UNIT? PLEASE SEE 422.30, 422.31 FOR THIS
 UNIT TO BE HARDWIRED AT A MINIMUM. MAY CONTAIN
 DISCONNECT AS NOTED, HOWEVER BREAKER IN PANEL MAY ALSO
 BE USED IF INDEED LOCATED IN PANEL ADJACENT TO UNIT.
 PLEASE CLARIFY.
  
 9) NOTE: PLEASE SEE THAT FIVE (5) SETS OF PLANS WERE
 SUBMITTED FOR REVIEW WHERE-AS ONLY TWO SETS ARE NEEDED
 FOR PERMITTING AND REVIEW. PLEASE KNOW THAT IF
 ADDITIONAL COPIES (UP TO THREE TOTAL) ARE REQUESTED TO
 BE STAMPED BY THE CITY, THEN PLEASE BE SURE THE
 ADDITIONAL THIRD SET IS SIGNED, DATED AND SEALED BY THE
 DESIGNER OF RECORD AS SHOWNON THE OTHER TWO SETS. FS
 481.221.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]