| 2007-02-28 07:39:55 | ** UNSAT ** |
| | |
| | ** PLEASE SEE OF THERE IS A SUITE TO THIS UNIT, PLEASE |
| | STATE ON PLANS. THIS IS TO VERIFIED WITH OUR ADDRESSING |
| | REVIEWER. |
| | |
| | 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST |
| | ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| | 8TH, 2006. |
| | 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS |
| | SUBMITTED |
| | 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED. |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE |
| | STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED |
| | IN THIS REVIEWER(S) COMMENTS. |
| | |
| | 2) NOTE:PLEASE SHOW ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH PANEL SCHEDULE(S). |
| | PLEASE SEE THERE ARE A FEW ITEMS ON PLANS WHICH STILL |
| | DO NOT SHOW THE CIRCUITING. |
| | PLEASE SEE ALL CIRCUITS WHICH REFLECT TO A PANEL AND |
| | CIRCUITS WHICH ARE NOT PART OF THE SUBMITTED PANEL |
| | SCHEDULES SUBMITTED. |
| | PLEASE ALSO SEE WATER FOUNTAIN HAS BEEN ADDED TO PLANS; |
| | HOWEVER PLANS DO NOT INDICATE ANY ELECTRICAL |
| | RECEPTACLES FOR THIS UNIT. |
| | PLEASE CORRELATE AND COORDINATE ALL. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE 517.12, 517.13, 517.60, 517.62 AND |
| | OTHER PARTS OF 517. PLEASE SPECIFY AREAS AND USE IN |
| | THESE AREAS. PLEASE SPECIFY ANY USE OF ANESTHETIZING |
| | LOCATIONS IF THIS APPLIES TO THIS OFFICE AND USE. |
| | PLEASE BE SURE TO PLACE NOTES FOR TYPE OF WIRING |
| | METHODS AND GROUNDING AS REQUIRED PER SECTIONS STATED. |
| | |
| | 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE |
| | PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE |
| | ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. |
| | PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION. |
| | |
| | 5) PLEASE SEE 700.12E FOR EMERGENCY AND EXIT LIGHTS. |
| | PLEASE KNOW AS CIRCUITING IS NOT SHOWN AT THIS TIME, |
| | COMPLIANCE FOR THIS CAN NOT BE VERIFIED. THESE SHALL BE |
| | CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT. |
| | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | 6) NOTE: PLEASE SHOW LOAD CALCULATIONS, PLEASE SHOW |
| | PER, 220.12, 220.14, 220.42, 220.44 ETC. |
| | PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER |
| | 215.3, AND 230.42 |
| | PLEASE INDICATE THE SIZE OF WHAT IS BEING SHOWN FOR THE |
| | EXISTING PANEL AND LOAD ON PANEL ALONG WITH NEW LOADS. |
| | |
| | 7) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| | CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE SEE BY DEFINITION THIS SPACE IS IN A BUILDING |
| | GREATER THAN 5K SQ FT. |
| | PLEASE SHOW COMPLIANCE WITH THIS AND IF THERE ARE ANY |
| | QUESTIONS, PLEASE CALL TO GO OVER THIS. |
| | PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC |
| | W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2 |
| | FOR LIGHTING PERFORMANCE CALCULATIONS ALONG WITH ENERGY |
| | CALCULATIONS. |
| | PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC |
| | FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE |
| | LPD/CALCULATIONS IS REVIEWED FOR COMPLIANCE. |
| | * PLEASE KNOW AS THE COMPLETE SCOPE OF WORK SEEMS TO BE |
| | MORE THAN APPLIED FOR ON PERMIT APPLICATION, ENERGY |
| | CALCULATIONS MAY ALSO BE REQUIRED FOR SPECIFIC |
| | USE/AREA. |
| | PLEASE BE SURE TO HAVE THE DESIGNER OF RECORD FOR THE |
| | ENERGY CALCULATIONS SIGN, DATE AND SEAL THESE AS |
| | REQUIRED PER 13-103.1.1.1 |
| | *PLEASE SEE NOTES ON PLANS MENTIONS SOME OF THESE AREAS |
| | AS EXISTING FOR NO WORK, YET PLANS INDICATE WORK BEING |
| | DONE IN THESE AREAS. |
| | |
| | 8) NOTE: PLEASE SEE PLAN WHERE WHAT SEEMS TO BE A WATER |
| | HEATER IN THE EQUIPMENT CLOSET WITH A RECEPTACLE TO |
| | *PLUG-IN* THIS UNIT? PLEASE SEE 422.30, 422.31 FOR THIS |
| | UNIT TO BE HARDWIRED AT A MINIMUM. MAY CONTAIN |
| | DISCONNECT AS NOTED, HOWEVER BREAKER IN PANEL MAY ALSO |
| | BE USED IF INDEED LOCATED IN PANEL ADJACENT TO UNIT. |
| | PLEASE CLARIFY. |
| | |
| | 9) NOTE: PLEASE SEE THAT FIVE (5) SETS OF PLANS WERE |
| | SUBMITTED FOR REVIEW WHERE-AS ONLY TWO SETS ARE NEEDED |
| | FOR PERMITTING AND REVIEW. PLEASE KNOW THAT IF |
| | ADDITIONAL COPIES (UP TO THREE TOTAL) ARE REQUESTED TO |
| | BE STAMPED BY THE CITY, THEN PLEASE BE SURE THE |
| | ADDITIONAL THIRD SET IS SIGNED, DATED AND SEALED BY THE |
| | DESIGNER OF RECORD AS SHOWNON THE OTHER TWO SETS. FS |
| | 481.221. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |