| Date |
Text |
| 2007-02-26 14:58:26 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS; CITY OF WEST PALM BEACH |
| | GAS PERMIT APPLICATION REQUIREMENTS; |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PLEASE INDICATE THE BTU LOAD OF EACH APPLIANCE AND |
| | THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: PLEASE INDICATE THE BTU LOADS OF THE APPLIANCES |
| | ON THE RESUBMITTAL. |
| | |
| | 2. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | NOTE: CLEARLY INDICATE THE DELIVERY PRESSURE ON THE |
| | RESUBMITTAL. THERE ARE TWO DELIVERY PRESSURES INDICATED |
| | ON THE SUBMITTED DRAWINGS, ONE IS 21 LB AND THE OTHER |
| | IS O.5 PSI, PLEASE CLARIFY ON THE RESUBMITTAL WITH ONLY |
| | INDICATING ONE DELVERY PRESSURE. |
| | |
| | 3. PLEASE CLEARLY INDICATE ON THE RESUBMITTAL IF THE |
| | GAS PIPING IS ABOVE GROUND OR UNDERGROUND, AND WHAT GAS |
| | PIPING IS EXISTING OR NEW. |
| | |
| | ******IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |
| | |