| Plan Review Notes For Permit 07020467 |
| Permit Number |
07020467 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-20 11:02:40 | ****************PROVISO**************** | | | GAS SYSTEM PER FBC-2004 FUEL GAS | | | TABLES: 402.4(2) AND 402.4(20). | | | | | | IF DRYER ROOM IS A CONFINED SPACE, OPENINGS | | | REQUIRED PER SECTION 304.5 OR | | | SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | | | IF WATER HEATER ROOM IS A CONFINED | | | SPACE, OPENINGS REQUIRED PER SECTION | | | 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 4,000 CUBIC FEET REQUIRED. | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | |
|