| 2007-06-04 07:48:18 | ** PROVISO ** |
| | |
| | ** REVISION REQUIRED WITHIN30 DAYS OF ISSUANCE OF |
| | PERMIT. |
| | |
| | 1) NOTE: PLEASE SEE AS STATED ON THE PREVIOUS REVIEW, |
| | WHEN THE AMOUNT OF DECORATIVE AND/OR RECESSED LIGHTING |
| | EXCEEDS THAT OF THE NORMAL 3VA PER SQ FT, THEN THE |
| | HIGHER AMOUNT SHALL BE FIGURED. PLEASE SEE THAT THE |
| | WATTAGE BASED ON THE AMOUNT OF EACH OF THESE TYPES OF |
| | FIXTURES DO EXCEED THE 3VA PER SQ FT.THIS WAS |
| | CONFIRMED BY THE CODE PANELIST AND THE AHJ IS THE |
| | DETERMINING AUTHORITY.PLEASE SEE THE FOLLOWING TEXT |
| | WHICH IS TAKEN DIRECTLY FROM THE 2005 NEC. |
| | |
| | *D) LUMINAIRES (LIGHTING FIXTURES) AN OUTLET SUPPLYING |
| | LUMINAIRE(S) [LIGHTING FIXTURE(S)] SHALL BE CALCULATED |
| | BASED ON THE MAXIMUM VOLT-AMPERE RATING OF THE |
| | EQUIPMENT AND LAMPS FOR WHICH THE LUMINAIRE(S) |
| | [FIXTURE(S)] IS RATED. |
| | IN GENERAL, NO ADDITIONAL CALCULATION IS REQUIRED FOR |
| | LUMINAIRES (RECESSED AND SURFACE MOUNTED) INSTALLED IN |
| | OR ON A DWELLING UNIT, BECAUSE THE LOAD OF SUCH |
| | LUMINAIRES IS COVERED IN THE 3 VOLT-AMPERES PER SQUARE |
| | FOOT CALCULATION SPECIFIED BY TABLE 220.12. WHERE THE |
| | RATING OF THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING |
| | EXCEEDS THE MINIMUM LOAD PROVIDED FOR IN TABLE 220.12, |
| | THE MINIMUM GENERAL LIGHTING LOAD FOR THAT PREMISES IS |
| | TO BE BASED ON THE INSTALLED LUMINAIRES. DISTINGUISHING |
| | BETWEEN THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING |
| | VERSUS THOSE INSTALLED FOR ACCENT, SPECIALTY OR DISPLAY |
| | LIGHTING IS MUCH EASIER TO DELINEATE IN COMMERCIAL |
| | (PARTICULARLY MERCANTILE) OCCUPANCIES. |
| | |
| | AS STATED, *IN GENERAL* AN ADDITIONAL AMOUNT IS NOT |
| | NEEDED ONLY WHEN THE FIXTURES ARE USED FOR NORMAL |
| | GENERAL LIGHTING. WHEN THE FIXTURES EXCEED THE GENERAL |
| | LIGHTING USE AS THIS IS DONE ON THIS PLAN, THEN THE |
| | ADDITIONAL SHALL BE FIGURED. |
| | THIS REVIEW IS BEING PASSED AS THE SERVICE IS KNOWN TO |
| | BE OF SUFFICIENT SIZE HOWEVER RECORD PLANS ARE TO BE |
| | CORRECTED FOR CODE COMPLIANCE. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-06-03 16:31:11 | IN ELEC FOR REVIEW. |