| Date |
Text |
| 2007-03-12 09:52:54 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS; THE CITY OF WEST PALM |
| | BEACH GAS PERMIT APPLICATION REQUIREMENTS; |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: NOT ALL |
| | CORRESPONDING LENGTHS ARE INDICATED. THE LONGEST LENGTH |
| | IS BEING INDICATED IS 88' BUT THE ADDED SUM OF THE |
| | INDICATED CORRESPONDING LENGTHS EQUALS 77'-6". PLEASE |
| | CORRECT AND CORRELATE ON THE RESUBMITTAL. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: THE ONLY |
| | INDICATED PIPING MATERIAL BEING USED IS PE FOR THE |
| | UNDERGROUND. ALL PIPING MATERIALS MUST BE INDICATED ON |
| | THE RESUBMITTAL. IF THE GAS TYPE IS NATURAL GAS WITH A |
| | DELIVERY PRESSURE OF 0.5 PSI PLEASE NOTE THE RED LINE |
| | CORRECTIONS TO THE GAS PIPE SIZES. PLEASE REFERENCE THE |
| | ATTACHED GAS SIZING TABLES TO THE GAS COMMENTS |
| | INDICATING THIS. PLEASE CORRECT AND RESUBMIT. |
| | |
| | 3. SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: THE TYPE OF |
| | GAS BEING USED SHALL BE CLEARLY INDICATED AS, (LP) OR |
| | (NATURAL). PLEASE CORRECT ON THE RESUBMITTAL. |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: THE TOTAL |
| | BTU'S ARE NOT CLEARLY INDICATED AND ARE BEING INDICATED |
| | WRONG AS 3?0,000. THE TOTAL SUM OF THE BTU'S SHOULD BE |
| | 410,000. PLEASE CORRECT ON THE RESUBMITTAL. |
| | ********IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |