| Plan Review Notes For Permit 07020466 |
| Permit Number |
07020466 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-23 10:04:41 | | | | | | | IF DRYER ROOM IS A CONFINED SPACE, OPENINGS REQUIRED | | | PER SECTION 304.5 OR | | | SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 1,000 CUBIC FEET REQUIRED. | | | | | | IF WATER HEATER ROOM IS A CONFINED | | | SPACE, OPENINGS REQUIRED PER SECTION | | | 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 2,000 CUBIC FEET REQUIRED. |
|