| Date |
Text |
| 2007-04-04 09:58:50 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PER FBC-2004, CHAPTER 1, SECTION |
| | 106.1.3, QUALITY OF BUILDING PLANS: THE |
| | BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| | POLICY, STANDARDS FOR PLANS |
| | AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, |
| | CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | NOTE: PLANS ARE HARD TO READ AND THE PIPING SCHEMATIC |
| | DOES NOT REFLECT THE POOL LAYOUT. PLEASE DELETE THE |
| | SPA, AND CLEANING LINE FROM THE SCHEMATIC ON THE |
| | RESUBMITTAL AND CLEARLY INDICATE THAT THESE ITEMS ARE |
| | NOT BEING USED IN THE "POOL DATA & EQUIPMENT & |
| | CRITERIA" ON THE RESUBMITTAL. |
| | |
| | 2. PER R4101.6.6.4 SUCTION INLETS PER PUMP THE TWO |
| | SUCTION INLETS ON THE PIPING DIAGRAM ARE INDICATED IN |
| | THE WRONG PLACE. IF IT IS THE INTENT TO LOCATE THE TWO |
| | SUCTION INLETS IN THE SIDE WALL THEY MUST BE ONE EACH |
| | ON TWO SEPERATE VERTICAL WALLS. PLEASE REFLECT THIS ON |
| | THE RESUBMITTAL. |
| | |
| | 3.FBC-2004 SEC. 424.2.7.2, OR |
| | FBCR-2004 SEC. R4101.7.2 PUMPS AND |
| | EQUIPMENT SHALL BE MOUNTED ON A |
| | SUBSTANTIAL BASE IN A MANNER THAT WILL |
| | ELIMINATE STRAIN ON PIPING.SLAB SHALL |
| | BE A NOMINAL 4" THICK. |
| | NOTE: PLEASE INDICATE ON THE RESUBMITTED POOL EQUIPMENT |
| | ANCHOR DETAIL THAT THE SLAB IS A NOMINAL 4 INCH THICK |
| | (4") |
| | |
| | 4. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. |
| | R4101.9 WATER SUPPLY, LOCAL ORD. |
| | #2853-95, BACKFLOW REQUIRED ON WATER |
| | SERVICE.(ADD TO NOTES) |
| | |
| | 5.FBC-2004 SEC. 424.2.14.4, OR |
| | FBCR-2004 SEC. R4101.14.4 CONNECTIONS, |
| | ALL WATER HEATING EQUIPMENT SHALL BE |
| | INSTALLED WITH FLANGES OR UNION |
| | CONNECTIONS ADJACENT TO THE HEATER. |
| | (ADD TO NOTES) |
| | |
| | 6.FBC-2004 SEC. 424.2.14, OR FBCR-2004 |
| | SEC. R4101.15 GAS PIPING SHALL COMPLY |
| | WITH FBC FUEL GAS.SEPARATE PLANS AND |
| | PERMIT REQUIRED. |
| | (ADD TO NOTES) |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |