| 2007-04-16 16:08:39 | DENIED BY BUILDING |
| | |
| | 1) ITEM NUMBER 2 FROM THE PREVIOUS REVIEW REQUIRES |
| | EXTERIOR WALLS TO SEPARATED BY A MINIMUM OF 6 FEET |
| | UNLESS WALLS HAVE A ONE HOUR FIRE-RESISTIVE RATING. |
| | THIS APPLIES TO STRUCTURES ON ADJACENT LOTS AS WELL AS |
| | BUILDINGS ON THE SAME LOT.THE REAR OF THE STRUCTURE |
| | APPEARS TO BE LOCATED ON THE PROPERTY LINE AND THE SIDE |
| | APPEARS TO BE LESS THAN SIX FEET FROM THE PROPERTY |
| | LINE.THEREFORE, A SITE PLAN SHOWING THE DISTANCE TO |
| | ANY STRUCTURES LOCATED ON ADJACENT LOTS IS REQUIRED FOR |
| | THESE WALLS OR THEY WILL BE REQUIRED TO BE ONE HOUR |
| | FIRE RATED AS REQUIRED BY R302.1. |
| | |
| | 2) ITEM NUMBER 5 ON THE PREVOIUS REVIEW REQUIRED THE |
| | MEAN ROOF HEIGHT SPECIFIED ON THE TRUSS LAYOUT TO BE |
| | CORRECTED FROM 15 FEET TO THE MEAN ROOF HEIGHT FOR A |
| | TWO STORY STRUCTURE. THE CORRECTION WAS DONE WITH |
| | WHITEOUT WHICH IS NOT ALLOWED ON SIGNED AND SEALED |
| | DRAWINGS. ANY CHANGES MADE TO THE TRUSS LAYOUT IS |
| | REQUIRED TO BE MADE BY THE TRUSS ENGINEER AND INITIALED |
| | AND DATED BY HIM. THE SIGNED AND SEALED TRUSS LAYOUT |
| | AND TRUSS DRAWINGS CAN BE SUBMITTED TO THE FIELD |
| | INSPECTOR PRIOR TO TRUSS INSPECTION. |
| | |
| | 3) THE PRODUCT APPROVAL SUBMITTED FOR THE ROOFING |
| | MATERIAL FOR THE BALCONY REQUESTED IN THE PREVIOUS |
| | REVIEW FOR ITEM #18 IS INCORRECT. THE GAF SYSTEM |
| | SUBMITTED IS FOR INSTALLATION OVER A CONCRETE DECK AND |
| | ON SHEET 5 A PLYWOOD DECK IS SPECIFIED AT THE BALCONY. |
| | PLEASE CORRECT. THE FL PRODUCT APPROVAL THAT WAS |
| | SUBMITTED IS FOR THE 2001 CODE VERSION. THE CURRENT |
| | CODE VERSION IS THE 2004 FBC. |
| | |
| | 4) ADDRESS ZONNING DEPARTMENT COMMENTS. |
| | |