| Plan Review Notes For Permit 07020441 |
| Permit Number |
07020441 |
|
| Review Stop |
Z |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-06 14:46:43 | ***FAILED*** | | | | | | DUMPSTER MUST BE A MINIMUM OF 5 FEET FROM PROPERTY | | | LINES. AS SHOWN, THE DUMPSTER IS TOO CLOSE TO THE SOUTH | | | PROPERTY LINE. | | | | | | THERE IS A FUTURE GENERATOR SHOWN ON THE PLUMBING | | | PLANS. BE AWARE THAT A GENERATOR MAY NOT BE PLACED IN | | | THIS LOCATION AS IT BLOCKS ACCESS TO THE PARKING AND | | | DRIVE AISLE. IT WOULD APPEAR THE ONLY VIABLE ON-GROUND | | | LOCATION WOULD BE IN THE PARKING ROW ALONG THE EAST | | | SIDE OF THE PROPERTY. THE BUILDING REQUIRES 14 PARKING | | | SPACES AND 16 ARE PROVIDED. TWO SPACES COULD BE REMOVED | | | TO ACCOMMODATE THE GENERATOR. PLEASE NOTE THAT | | | GENERATORS SHALL BE SCREENED TO THE SAME STANDARDS AS | | | DUMPSTER ENCLOSURES. DEPENDING ON YOUR FUTURE PLANS, IT | | | MAY BE PRUDENT TO CONSTRUCT A COMBINATION | | | DUMPSTER/GENERATOR ENCLOSURE SO THAT A FUTURE GENERATOR | | | MAY BE ACCOMMODATED PER CODE REQUIREMENTS. | | | | | | PLEASE SHOW CODE COMPLIANT STRIPING ON ALL PARKING | | | SPACES. | | | | | | PLEASE CALL KELLY FREEMAN, PLANNER, AT 561-822-1435 | | | WITH QUESTIONS. |
|