| 2007-03-13 13:55:54 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT A-3 SHOW THE CLEAR FLOOR SPACE FOR THE W/C'S PER |
| | SECTION 11-4.16.2, THE DRINKING FOUNTAIN PER SECTION |
| | 11-4.15.5, AND THE KITCHEN SINK PER SECTION 11-4.24.5, |
| | (FORWARD APPROACH REQUIRED). |
| | |
| | 2. SHT A-8 PLUMBING SANITARY RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| | REQUIREMENTS. TOILET ROOMS #2 SHOW A W/C & A LAV IN |
| | EACH ROOM ON THE FLOOR PLAN, BUT ON THE RISER DIAGRAM |
| | AS DRAWN IT INDICATES BOTH W/C'S IN ONE ROOM AND BOTH |
| | LAVS IN ANOTHER. ALSO THE W/C'S ARE SHOWN CONNECTING TO |
| | THE BRANCH LINE & TO THE BUILDING DRAIN LINE. W/C'S |
| | SHALL BE CONNECTED TO THE BRANCH LINE ONLY.--ONLY |
| | THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| | ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE |
| | WET VENT. SECTION 909.1. ALL OTHER FIXTURES BESIDES THE |
| | FIXTURES IN TOILET ROOMS #2 SHALL CONNECT DOWNSTREAM OF |
| | THE FIXTURES ON TOILET ROOMS #2.--TOILET ROOMS #1 |
| | ARE SHOWN ON THE LEFT OF TOILET ROOMS #2 ON THE FLOOR |
| | PLAN, BUT ARE SHOWN ON THE RIGHT SIDE OF TOILET ROOMS |
| | #2 ON THE RISER DIGARAM.--THE DRINKING FOUNTAIN IS |
| | NOT SHOWN ON THE RISER DIAGRAM. CORRELATE FLOOR PLAN |
| | AND RISER. SECTION 106.1.1.--THE LAVS AND W/C'S IN |
| | TOILET ROOMS #1 ARE NOT VENTED AS SHOWN. SECTION |
| | 901.2.1.--TRAPS ARE NOT ALLOWED FOR THE W/C'S AS |
| | THEY HAVE INTEGRAL TRAPS BUILT IN THEM. SECTION 1002.1. |
| | (SEE ONE SET OF PLANS SHT A-8 FOR AN EXAMPLE OF A RISER |
| | DIAGRAM THAT REFLECTS THE FLOOR PLAN AND MEETS CODE |
| | REQUIREMENTS). |
| | |
| | 3. SUBMIT A WATER RISER DIAGRAM THAT REFLECT THE FLOOR |
| | PLAN. SHOW ALL PIPE SIZES, VALVES ECT. SECTION |
| | 106.3.5.1.3(3)(10)(13). |
| | |
| | 4. SUBMIT THE FOLLOWING INFORMATION FOR THE REQUIRED |
| | GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. (SHOW THE LENGTH FROM THE METER TO THE |
| | FIRST RISER), |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | H. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | I. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | 5. SHT A-8 SHOW COMPLIANCE FOR THE FOLLOWING: |
| | FOR THE LAVS: |
| | A. 11-4.19.2 CLEARANCE (29") |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.91.5 FAUCETS |
| | |
| | 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15AND ALL SUBSECTIONS, AS |
| | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. SECTION |
| | 106.1.1. |
| | |
| | 7. SUBMIT A DETAIL FOR THE KITCHEN SINK SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | SUBMIT AN ELEVATION VIEW. CABINET DOORS ARE NOT |
| | APPROVED FOR THE SINK AREA. SECTION 106.1.1. |
| | |