| Plan Review Notes For Permit 07020441 |
| Permit Number |
07020441 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-17 16:53:40 | ------------------DENIED------------------- | | | | | | 1. PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON PLANS. FBC | | | 106.3.5.1.4 | | | | | | 2. PLEASE PROVIDE SUBMITTAL DATA FOR THE FIREPLACE | | | INCLUDING MANUFACTURER'S INSTRUCTIONS RELATED TO | | | VENTING REQUIREMENTS. | | | | | | 3. DUCT SMOKE DETECTORS SHALL BE INSTALLED TO MONITOR | | | THE ENTIRE AIRFLOW OF THE SYSTEM PER FBC,M 606.3. TO | | | ACCOMPLISH THIS, THE DETECTOR NEEDS TO BE LOCATED IN | | | THE SUPPLY TRUNK BEFORE FIRST TAP OR BRANCH DUCT. | | | CONSULT THE MANUFACTURER'S INSTALLATION INSTRUCTIONS | | | FOR MINIMUM REQUIRED DISTANCE FROM BLOWER. AN | | | AUDIBLE/VISIBLE NOTIFICATION (HORN/STROBE) IN AN | | | APPROVED LOCATION IS REQUIRED UPON ACTIVATION OF THE | | | SMOKE DETECTOR PER FBC,M 606.4.1(2) | | | | | | 4. SOME TRANSFER DUCTS (JUMPERS) ARE NOT SIZED TO MEET | | | THE BALANCED RETURN AIR EXCEPTIONS AS LISTED IN FBC,M | | | 601.4. IF THESE EXCEPTIONS ARE NOT MET, A FIELD TEST | | | WILL BE REQUIRED AT FINAL INSPECTION TO SHOW THAT THE | | | REQUIREMENT FOR A MAXIMUM PRESSURE DIFFERENTIAL OF | | | 0.01" WC HAS BEEN ACHIEVED. | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|