| Plan Review Notes For Permit 07020441 |
| Permit Number |
07020441 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-29 14:08:42 | *****DENIED***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.NFPA 101- 2003 EDITION SHALL BE REFERENCED. | | | | | | 3.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE | | | CLASS A OR CLASS B IN EXITS AND EXIT CORRIDORS, CLASS | | | A, CLASS B, OR CLASS C IN ALL OTHER AREAS.PLEASE | | | SPECIFY. | | | | | | 4.SHOW LOCATION OF THE 2A10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE. | | | | | | 5.IF THE BUILDING IS EQUIPPED WITH A FIRE ALARM AND | | | (OR) FIRE SPRINKLER SYSTEM, WILL THE SCOPE OF WORK | | | CAUSE THE SYSTEM(S) TO BE MODIFIED?IF SO, SEPARATE | | | PLANS AND PERMIT WILL BE REQUIRED FOR THE REMODEL. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|