| 2007-03-04 17:09:14 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWINGON ELECTRICAL SHEETS FOR |
| | THIS REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS.(ALREADY ON MAIN |
| | ARCHITECTURAL SHEETS) |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR |
| | ARCHITECT AND FIRM AS REQUIRED UNDER FLORIDA |
| | ADMINISTRATIVE CODE 61G1-16.004. PLEASE ALSO SEE |
| | FLORIDA STATUTES AND 481.219. |
| | PLEASE SEE MISSING THE REQUIRED PRINTED NAME AND |
| | PRINTED LICENSE NUMBER OF DESIGNER AND MISSING FIRM |
| | LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | |
| | 3) NOTE:PLEASE SUBMIT ENERGY/PERFORMANCE CALCULATIONS |
| | FOR NEW LIGHTING WHICH CORRELATES WITH THE ELECTRICAL |
| | PLANS AND LIGHTING SHOWN. PLEASE SEE LIGHTING AS SHOWN |
| | ON CALCULATIONS DOES NOT CORRELATE. |
| | PLEASE ALSO BE SURE THESE ARE SIGNED, DATED AND SEALED |
| | BY THE DESIGNER OF RECORD AND THE PERSON RESPONSIBLE |
| | FOR ENERGY CALCULATIONS. |
| | PLEASE SEE THAT AN AUTOMATED METHOD OF LIGHTING |
| | CONTROLS IS BEING NOTED ON SYMBOL LEGEND HOWEVER THE |
| | ENERGY CALCULATIONS DO NOT CORRELATE WITH THIS AS THEY |
| | SHOW *MANUAL ON/OFF* FOR THIS? |
| | PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED |
| | FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS |
| | ON THE ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS. |
| | PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1, |
| | 13-415.1.AB.1.1, 13-415.2,AND 13-415.2.ABC.1.2 (3) |
| | FOR TRACK LIGHTING (WHERE APPLICABLE) |
| | |
| | 4) NOTE: PLEASE SEE THAT PLANS DO INDICATE SOME |
| | CONTROLS FOR LIGHTING HOWEVER PLEASE SUBMIT MORE |
| | INFORMATION FOR SYSTEM BEING PROPOSED. |
| | FBC 106.1.2 ADMIN SECTION |
| | 110.3, 90.7 NEC. |
| | |
| | 5) NOTE: PLEASE SEE THE ACCESS TO THE ELECTRICAL ROOM |
| | WILL NOT BE PERMITTED THROUGH A STORAGE ROOM. 240.24. |
| | PLEASE KNOW THAT ALL ACCESS TO OVER CURRENT PROTECTION |
| | DEVICES SHALL BE ACCESSIBLE ON A CONTINUING BASIS. |
| | PLEASE KNOW THIS IS REQUIRED BY THIS OFFICE AND THE |
| | OFFICE OF THE FIRE MARSHAL. |
| | PLEASE SEE THE LOCATION OF THE PANEL *D* IS BEING NOTED |
| | AND SHOWN IN A STORAGE ROOM WHICH IS NOT PERMITTED. |
| | PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE |
| | ELECTRICAL PANEL(S) NEED TO MEET 110.26. |
| | PLEASE ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY |
| | IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES |
| | WITH OVER CURRENT PROTECTION DEVICES. |
| | PLEASE ADJUST PLANS. |
| | |
| | 6) NOTE:PLEASE SEE PLANS ON ARCHITECTURAL SHEETS |
| | NOTES SERVICE AS EXISTING HOWEVER THE ELECTRICAL PLANS |
| | AND RISER SEEM TO NOTE AND INDICATE ALL OF THIS |
| | EQUIPMENT AS NEW. PLEASE CLARIFY AND ADJUST NOTE ON |
| | ARCHITECTURAL PLANS IF ALL NEW AS SHOWN. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 7) NOTE: PLEASE KNOW THAT THE PLANS NEED TO CORRELATE |
| | WITH ALL CIRCUIT DESIGNATIONS ON PLANS FOR ROOMS AND |
| | AREAS. PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY |
| | IN THE CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT |
| | ACCEPTABLE. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS THE |
| | M-SHEETS DO NOT SEEM TO INDICATE ANY MECHANICAL |
| | EQUIPMENT. PLEASE KNOW THAT REVIEW OF EQUIPMENT FOR |
| | ELECTRICAL COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | PLEASE COMPLETE. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 9) NOTE: PLEASE SEE PANEL SCHEDULE *A* IS NOT COMPLETE |
| | FOR CONDUCTOR SIZES REQUIRED FOR AC EQUIPMENT. PLEASE |
| | ALSO SEE MISSING LOAD FOR THE RTU. |
| | PLEASE COMPLETE FOR REVIEW OF CODE COMPLIANCE. 310.16, |
| | 240.4, 220, 408.4 |
| | |
| | 10) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF |
| | EMERGENCY AND EXIT LIGHTS. PLEASE SEE MOST ARE |
| | CIRCUITED CORRECTLY AND ONLY ONE OR SO IS CIRCUITED TO |
| | OTHER THAN THE LOCAL LIGHTING BRANCH CIRCUIT. |
| | |
| | 11) NOTE: PLEASE CLARIFY MEZZANINE LEVEL FOR LIGHTING |
| | AND CONTROL. |
| | PLEASE KNOW LIGHTING CONTROL WILL ALSO BE REQUIRED AT |
| | THE MEZZ LEVEL AND RECEPTACLE FOR SERVICE PER 210.63, |
| | 210.70. |
| | |
| | 12) NOTE: PLEASE SEE PANEL *C* ON RISER WHICH DOES NOT |
| | CORRELATE WITH THE NUMERICAL ELECTRICAL RISER NOTE. |
| | PLEASE SEE NOTE MENTIONS 100AMP PANEL WITH A 200AMP |
| | MAIN BREAKER YET PANEL SCHEDULE SHOWS THIS PANEL AS |
| | 150AMPS? |
| | |
| | 13) NOTE: PLEASE SEE PANEL *B* AND NOTE ABOVE FOR PANEL |
| | *C*. PLEASE CORRELATE WITH ELECTRICAL NOTES ALSO AND |
| | THE RISER WHICH SHOWS NOTE #10. NOTE #10 IS ALSO USED |
| | FOR PANEL *D*. |
| | PLEASE CORRELATE. |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION. |
| | |
| | 14) NOTE: PLEASE SEE NOTE FOR GROUNDING ELECTRODE |
| | SYSTEM MENTIONS NEW *BLDG STEEL* YET THIS BEING AN |
| | EXISTING BUILDING IT IS UNCLEAR WHERE THE NEW BUILDING |
| | STEEL IS BEING SHOWN. REVIEW OF ARCHITECTURAL AND |
| | STRUCTURAL PLANS DOES NOT REVEAL THIS. |
| | PLEASE KNOW AS AN EXISTING BUILDING THE FOOTER STEEL IS |
| | NOT A REQUIRED ATTACHMENT UNLESS NEW.OPENING OF THE |
| | OLDER EXISTING FOOTER TO MAKE AN ATTACHMENT COULD |
| | CREATE ISSUES FOR THE STRUCTURAL INTEGRITY OF THE |
| | EXISTING FOOTER DEPENDING ON THE AGE ETC. |
| | 250.50 |
| | |
| | 15) NOTE: PLEASE CORRELATE THE CIRCUITING FOR CLOCK |
| | FEED AS THE LOAD AND AMPERAGE ON THE PANEL SCHEDULE, |
| | PLANSAND LOAD CALCULATIONS LEND THIS TO BE A 20AMP |
| | AND SINGLE POLE CIRCUIT, HOWEVER THE PANEL SCHEDULE |
| | SHOWS THIS FEED AS A 2-POLE 30AMP CIRCUIT WITH #10 |
| | AWG? |
| | PLEASE CORRELATE. |
| | FBC 106.3.5.1.2 |
| | |
| | 16) NOTE: PLEASE SEE PANEL *D* NOTE WHICH MENTIONS THIS |
| | AS A 200AMP MCB PANEL YET, PANEL IS SHOWN AS MLO. FBC |
| | 106.3.5.1.2, 106.1.2 FOR COORDINATION. |
| | |
| | ** PLEASE KNOW AS SOME INFORMATION IS NOT SUBMITTED AT |
| | THIS TIME FOR REVIEW THER MAY BE COMMENTS ON ANY |
| | FOLLOWING REVIEWS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |