| 2007-03-15 16:21:46 | BUILDING PLAN REVIEW |
| | PERMIT: 07020441 |
| | ADD: 6600S DIXIE HWY |
| | CONT: S. E. C. CONSTRUCTION & DEV |
| | TEL: (561)797-6007 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1) --- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH |
| | NOTICE IS NULL & VOID. NOTE: 713.13(6) THE POSTING OF |
| | THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3) COVER SHEET A-1 DESIGN DATA INDICATES THE DESIGN TO |
| | ASCE 7-98, THE CURRENT STANDARD UNDER THE 2006 FBC IS |
| | ASCE 7-02. |
| | |
| | 4) PLANS ALSO INDICATE THERE ARE NO OPENINGS IN END |
| | ZONES, 10% OF 55'-2"OR 5'-2" OR 40% OF BUILDING MEAN |
| | ROOF HEIGTH13'-0"= 5'-21/2", PLEASE CORRECT THE WINDOWS |
| | PRESSURES IN THE END ZONES. TABLE 1609.6B. |
| | |
| | 5) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 6) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7) FRONT DOOR TO BE BUILT AS A ONE TIME APPROVAL , THE |
| | DESIGNER OF RECORD WILL NEED TO SUPERVISE |
| | THE ASSEMBLY OF THE DOOR AND THE INSTALATION OF DOOR |
| | AND FRAME, AND SIGN AND SEAL AFFADAVIT TO THE EFFECT. |
| | THIS WILL BE A PROVISO REQUIRED BEFORE A CERTIFICATE OF |
| | COMPLETION CAN BE ISSUED. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |