2007-11-06 11:57:17PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 FROM REVIEW DONE ON 10-30-07. 1) REVISED COOLING LOAD
 CALCULATIONS FOR A/C SYSTEM #3 IS CALLING FOR 17,439
 TOTAL BTU'S. REVISED MECHANICAL PLANS FOR A/C SYSTEM #3
 ARE CALLING FOR 23,400 TOTAL BTU'S. THE PLANS CAN ONLY
 CALL FOR 15% MORE TOTAL BTU'S. THAN THE COOLING LOAD
 CAL'S. SEE FBC 13-607.1.ABC.1.1. PLEASE CORRECT PLANS
  
 *** YOUR RESPONSE TO COMENT WAS TO CHANGE THE TOTAL
 BTU'S ON THE PLAN TO 17,800. THE SYSTEM IS STILL A TWO
 TON SYSTEM AND STILL HAS 23,400 TOTAL BTU'S IF UNCERTIN
 SEE THE INFORMATION FOR SYSTEM #1 AND #2 WHICH ARE THE
 SAME SYSTEM AS #3. ALL THAT HAS BEEN DONE IS THE
 INFORMATION ON THE PLAN HAS BEEN CHANGED SO THAT THE
 BTU'S DO NOT CORRALATE WITH THE MANUFACTURE'S SPEC'S..
 ONE POSSIBLE CORRECT ACTION MAY HAVE BEEN TO CHANGE THE
 SYSTEM TO A 1.5 TON. SEE ATTACHED ARI PRINT-OUT FOR 1.5
 AND 2 TON SYSTEMS.
  
 *** BE ADVISED A COPY OF THE PLAN HAS BEEN RETAINED FOR
 OUR RECORDS.
  