| 2007-10-30 15:42:58 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | MECHANICAL REVISION | | | *** DENIED *** | | | 1) REVISED COOLING LOAD CALCULATIONS FOR A/C SYSTEM #3 | | | IS CALLING FOR 17,439 TOTAL BTU'S. REVISED MECHANICAL | | | PLANS FOR A/C SYSTEM 3# ARE CALLING FOR 23,400 TOTAL | | | BTU'S. THE PLANS CAN ONLY CALL FOR 15% MORE TOTAL | | | BTU'S. THAN THE COOLING LOAD CAL'S. SEE FBC | | | 13-607.1.ABC.1.1. PLEASE CORRECT PLANS | | | | | | 2) PLEASE SHOW ON PLAN A/C SYSTEM MANUFACTURER,S NAME | | | (CARRIER). | | | | | | 3) RETURN AIR DUCT FROM AHU #1 TO RETURN AIR GRILL IN | | | HALLWAY NEEDS TO BE SIZED, SEE WPB AMEND. 106.3.5.4 | | | (10). | | | | | | 4) ALL THE SUPPLY AIR DUCTS FROM AHU #3 IN REC. ROOM | | | NEED TO BE SIZED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|