2007-10-30 15:42:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) REVISED COOLING LOAD CALCULATIONS FOR A/C SYSTEM #3
 IS CALLING FOR 17,439 TOTAL BTU'S. REVISED MECHANICAL
 PLANS FOR A/C SYSTEM 3# ARE CALLING FOR 23,400 TOTAL
 BTU'S. THE PLANS CAN ONLY CALL FOR 15% MORE TOTAL
 BTU'S. THAN THE COOLING LOAD CAL'S. SEE FBC
 13-607.1.ABC.1.1. PLEASE CORRECT PLANS
  
 2) PLEASE SHOW ON PLAN A/C SYSTEM MANUFACTURER,S NAME
 (CARRIER).
  
 3) RETURN AIR DUCT FROM AHU #1 TO RETURN AIR GRILL IN
 HALLWAY NEEDS TO BE SIZED, SEE WPB AMEND. 106.3.5.4
 (10).
  
 4) ALL THE SUPPLY AIR DUCTS FROM AHU #3 IN REC. ROOM
 NEED TO BE SIZED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]