| 2007-04-20 13:59:16 | *** PROVISO *** |
| | 1) DUCTS IN THE GARAGE AND DUCTS PENETRATING THE WALLS |
| | OR CEILINGS SEPARATING THE DWELLING FROM THE GARAGE |
| | SHALL BE CONSTRUCTED OF A MINIMUM NO. 26 GAGE SHEET |
| | STEEL OR OTHER APPROVED |
| | MATERIAL AND SHALL HAVE NO OPENINGS INTO THE GARAGE. |
| | PER 2004 FBC/R 309.1.1 . |
| | |
| | 2) 2004 FBC/R M1305.1.3 APPLIANCES IN ATTICS. |
| | ATTICS CONTAINING APPLIANCES REQUIRING ACCESS SHALL BE |
| | PROVIDED WITH AN OPENING AND UNOBSTRUCTED PASSAGEWAY |
| | LARGE ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE. |
| | THE PASSAGEWAY SHALL NOT BE LESS THAN 30 INCHES (762 |
| | MM) HIGH AND 22 INCHES (559 MM) WIDE AND NOT MORE THAN |
| | 6 FEET (1829 MM) IN LENGTH MEASURED ALONG THE |
| | CENTERLINE OF THE PASSAGEWAY FROM THE ATTIC ACCESS |
| | OPENING TO THE APPLIANCE?S SERVICE PANEL. THE |
| | PASSAGEWAY SHALL HAVE CONTINUOUS SOLID FLOORING NOT |
| | LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE |
| | SPACE NOT LESS THAN 30 INCHES (762 MM) DEEP AND 30 |
| | INCHES (762 MM) WIDE SHALL BE PRESENT AT THE FRONT OR |
| | SERVICE SIDE OF THE APPLIANCE. THE CLEAR ACCESS OPENING |
| | DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES |
| | (508 MM BY 762 MM), WHERE SUCH DIMENSIONS ARE LARGE |
| | ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE. |
| | EXCEPTION: THE PASSAGEWAY AND LEVEL SERVICE SPACE ARE |
| | NOT REQUIRED WHERE THE APPLIANCE IS CAPABLE OF BEING |
| | SERVICED AND REMOVED THROUGH THE REQUIRED OPENING. |
| | |