| 2007-04-30 10:21:07 | DENIED BY BUILDING |
| | |
| | 1) THE NOTICE OF COMMENCEMENT THAT WAS SUBMITTED IS |
| | EXPIRED AND WILL NEED TO BE RERECORDED. WORK MUST |
| | COMMENCE WITHIN 90 DAYS OF THE DATE THE NOC IS |
| | RECORDED. SEE FS 713. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT PRODUCT APPROVALS FOR THE SINGLE HUNG WINDOW |
| | IN THE NEW WALL OF EXISTING BATHROOM #2 SPECIFIED ON |
| | THE FLOOR PLAN ON 3.1. THE ELEVATION ON 5.1 SHOWS A |
| | CASEMENT WINDOW AT THIS LOCATION. |
| | |
| | 4) PROVIDE DETAILS OF THE CORNER FIXED GLASS WINDOWS AT |
| | THE FAMILY ROOM AND MASTER BEDROOM. SPECIFY THE GLASS |
| | SIZES AND HOW THEY ARE CONNECTED IN THE CORNERS. |
| | PROVIDE PRODUCT APPROVALS FOR THE ASSEMBLY. IF THESE |
| | ARE BUTT GLASS WINDOWS SITE SPECIFIC ENGINEERING WILL |
| | BE REQUIRED. IF NOT SUBMIT PRODUCT APPROVALS. |
| | |
| | 5) THE SPIRAL STAIRS SERVING AS THE MEANS OF EGRESS |
| | FROM THE ROOM ABOVE THE GARAGE IS REQUIRED TO COMPLY |
| | WITH R311.5.8.1 SPIRAL STAIRWAYS. SHOW COMPLIANCE. |
| | SPIRAL STAIRWAYS ARE PERMITTED, PROVIDED THE MINIMUM |
| | WIDTH SHALL BE 26 INCHES (660 MM) WITH EACH TREAD |
| | HAVING A 7-1/2 INCHES (190 MM) MINIMUM TREAD DEPTH AT |
| | 12 INCHES FROM THE NARROWER EDGE. ALL TREADS SHALL BE |
| | IDENTICAL, AND THE RISE SHALL BE NO MORE THAN 9-1/2 |
| | INCHES (241 MM). A MINIMUM HEADROOM OF 6 FEET 6 INCHES |
| | (1982 MM) SHALL BE PROVIDED. REVISE DETAIL ON 3.1 TO |
| | SPECIFY 7-1/2 " TREAD WIDTH AT 12 ". SHOP DRAWINGS WILL |
| | BE REQUIRED TO BE SUBMITTED FOR APPROVAL BEFORE |
| | INSTALLATION. |
| | |
| | 6) SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED. THE |
| | GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND ITS |
| | ATTIC AREA BY NOT LESS THAN 1/2 -INCH (12.7 MM) GYPSUM |
| | BOARD APPLIED TO THE GARAGE SIDE. GARAGES BENEATH |
| | HABITABLE ROOMS SHALL BE SEPARATED FROM ALL HABITABLE |
| | ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH (15.9 MM) TYPE |
| | X GYPSUM BOARD OR EQUIVALENT. WHERE THE SEPARATION IS A |
| | FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE |
| | SEPARATION SHALL ALSO BE PROTECTED BY NOT LESS THAN 1/2 |
| | -INCH (12.7 MM) GYPSUM BOARD OR EQUIVALENT. SPECIFY |
| | TYPE X GYPSUM BOARD AT THE GARAGE CEILING ON SECTION 1 |
| | ON 5.1. |
| | |
| | 7) THE CONNECTOR SCHEDULE ON 5.1 SPECIFIES TITEN SCREWS |
| | FOR NUMBER 4 , THE SIMPSON HGT-2 CONNECTOR. THE SIMPSON |
| | CATALOG REQUIRES THIS CONNECTOR TO BE ATTACHED TO THE |
| | CONCRETE BEAM WITH WITH TWO 3/4" DIA. THREADED ROD |
| | EPOXIED INTO BEAM WITH MINIMUM 12" EMBEDMENT. |
| | |
| | PLEASE SUBMIT A RESPONSE LETTER STATING HOW THESE |
| | COMMENTS HAVE BEEN ADDRESSED. |
| | |
| | NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE RESPONSES |
| | TO THESE COMMENTS. |
| | |