2007-03-01 08:18:51*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) ENERGY CALCULATIONS ARE CALLING FOR ONE 13.30 SEER
 AND TWO 15.80 SEER A/C SYSTEMS, MANUAL J CALCULATIONS
 ARE CALLING FOR ONE 14 SEER AND TWO 13 SEER A/C
 SYSTEMS. THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 3) PLEASE SHOW AN A/C EQUIPMENT LISTING ON THE
 MECHANICAL PLANS.
  
 4) PLEASE SHOW THE LOCATION OF THE WATER HEATERS ON THE
 PLANS.
  
 5) THE 9" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE
 NEEDS TO BE 14". SEE 2004 FBC/R M1602.4 (A) AND (C)
 EXCEPT, PLEASE CORRECT.
  
 ** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.