| 2007-03-01 08:18:51 | *** DENIED *** |
| | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 2) ENERGY CALCULATIONS ARE CALLING FOR ONE 13.30 SEER |
| | AND TWO 15.80 SEER A/C SYSTEMS, MANUAL J CALCULATIONS |
| | ARE CALLING FOR ONE 14 SEER AND TWO 13 SEER A/C |
| | SYSTEMS. THE TWO MUST COINCIDE, PLEASE CORRECT. |
| | |
| | 3) PLEASE SHOW AN A/C EQUIPMENT LISTING ON THE |
| | MECHANICAL PLANS. |
| | |
| | 4) PLEASE SHOW THE LOCATION OF THE WATER HEATERS ON THE |
| | PLANS. |
| | |
| | 5) THE 9" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE |
| | NEEDS TO BE 14". SEE 2004 FBC/R M1602.4 (A) AND (C) |
| | EXCEPT, PLEASE CORRECT. |
| | |
| | ** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE |
| | ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. |
| | |