 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER
 250.118, SIZED PER 250.122.
  
 2} INDICATE THE SIZE OF THE OVERCURRENT DEVICE IN THE
 MAIN DISCONNECT. 215.5.
  
 3} THE RECIRCULAING PUMP AND MICROWAVE IN THE LOAD
 CALCULATION ARE NOT LISTED ON THE PANEL SCHEDULE.
 PLEASE CORRELATE.
  
 4} THE IRRIGATION PUMP ON THE PANEL SCHEDULE IS NOT IN
 THE LOAD CALCULATION, PLEASE CORRELATE.
  
 5} ALL BATH CIRCUITS ARE REQUIRED TO HAVE A 20 AMP
 RECEPTACLE PER 210.11(C) (3), ONLY BATH #2 IS LISTED ON
 THE SCHEDULE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  