Notes
Date Text
2007-04-02 11:38:01DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) STRUCTURE IS LOCATED LESS THAN 6 FEET TO PROPERTY
 LINE. INDICATE THE DISTANCE TO STRUCTURES ON ADJACENT
 LOTS.
 R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.
 EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING
 LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE
 PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4
 INCHES (102 MM).
 PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM)
 SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR
 FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE
 PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND
 SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL
 PROTECTION BASED ON LOCATION ON THE LOT.
  
 4) SHOW COMPLIANCE WITH R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE.
 EXCEPTIONS:
 1.OPENINGS SHALL BE PERMITTED IN WALLS THAT ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 2.FOUNDATION VENTS INSTALLED IN COMPLIANCE WITH
 THIS CODE ARE PERMITTED.
  
 5) SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH
 R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 6) ON SHEET 2.1 SPECIFY THE THICKNESS FOR THE 24" WIDE
 SPREAD FOOTING F4. ALSO THERE IS A TYPO OF A 0 AFTER
 THE 3. PLEASE CORRECT.
  
 7) ON SHEET 2.1 SPECIFY THE DIMENSIONS OF THE STAIR
 FOOTING F8.
  
 8) PROVIDE DETAILS OF THE CORNER FIXED GLASS WINDOWS AT
 THE FAMILY ROOM AND MASTERBEDROOM. SPECIFY THE GLASS
 SIZES AND HOW THEY ARE CONNECTED IN THE CORNERS.
 PROVIDE PRODUCT APPROVALS FOR THE ASSEMBLY.
  
 9) ONE OF THE BATHROOMS ON THE FIRST FLOOR IS REQUIRED
 TO HAVE A 29" CLEAR OPENING. SEE FBC CHAPTER 11.
  
 10) THIS IS A LEVEL 3 ALTERATION. PLEASE CORRECT THE
 INFORMATION SPECIFIED UNDER PROJECT DATA ON SHEET 3.1.
  
 11) SAFETY GLAZING IS REQUIRED IN THE MASTER BATH ROOM
 AND OTHER TWO UPSTAIRS BATHROOMS PER FBC R308.3. IMPACT
 RATED GLAZING IS ACCEPTABLE IN THESE LOCATIONS.
  
 12) THE CASEMENT WINDOW IN UPSTAIRS BEDROOM #2 IS
 REQUIRED TO COMPLY WITH R310.1 FOR EMERGENCY ESCAPE AND
 RESCUE OPENINGS.
  
 13) THE SPIRAL STAIRS SERVING AS THE MEANS OF EGRESS
 FROM THE ROOM ABOVE THE GARAGE IS REQUIRED TO COMPLY
 WITH R311.5.8.1 SPIRAL STAIRWAYS. SHOW COMPLIANCE.
 SPIRAL STAIRWAYS ARE PERMITTED, PROVIDED TH E MINIMUM
 WIDTH SHALL BE 26 INCHES (660 MM) WITH EACH TREAD
 HAVING A 7?-INCHES (190 MM) MINIMUM TREAD DEPTH AT 12
 INCHES FROM THE NARROWER EDGE. ALL TREADS SHALL BE
 IDENTICAL, AND THE RISE SHALL BE NO MORE THAN 9? INCHES
 (241 MM). A MINIMUM HEADROOM OF 6 FEET 6 INCHES (1982
 MM) SHALL BE PROVIDED.
  
 14) SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED.
 THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND
 ITS ATTIC AREA BY NOT LESS THAN ? -INCH (12.7 MM)
 GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES
 BENEATH HABITABLE ROOMS SHALL BE SEPARATED FROM ALL
 HABITABLE ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH
 (15.9 MM) TYPE X GYPSUM BOARD OR EQUIVALENT. WHERE THE
 SEPARATION IS A FLOOR-CEILING ASSEMBLY, THE STRUCTURE
 SUPPORTING THE SEPARATION SHALL ALSO BE PROTECTED BY
 NOT LESS THAN ?-INCH (12.7 MM) GYPSUM BOARD OR
 EQUIVALENT.
  
 15) THE EXIT DOOR FROM THE ROOM ABOVE THE GARAGE IS
 REQUIRED TO COMPLY WITH R311.4.1 EXIT DOOR REQUIRED.
 NOT LESS THAN ONE EXIT DOOR CONFORMING TO THIS SECTION
 SHALL BE PROVIDED FOR EACH DWELLING UNIT. THE REQUIRED
 EXIT DOOR SHALL PROVIDE FOR DIRECT ACCESS FROM THE
 HABITABLE PORTIONS OF THE DWELLING TO THE EXTERIOR
 WITHOUT REQUIRING TRAVEL THROUGH A GARAGE. ACCESS TO
 HABITABLE LEVELS NOT HAVING AN EXIT IN ACCORDANCE WITH
 THIS SECTION SHALL BE BY A RAMP IN ACCORDANCE WITH
 SECTION R311.6 OR A STAIRWAY IN ACCORDANCE WITH SECTION
 R311.5 .
 R311.4.2 DOOR TYPE AND SIZE.
 THE REQUIRED EXIT DOOR SHALL BE A SIDE-HINGED DOOR NOT
 LESS THAN 3 FEET (914 MM) IN WIDTH AND 6 FEET 8 INCHES
 (2032 MM) IN HEIGHT. OTHER DOORS SHALL NOT BE REQUIRED
 TO COMPLY WITH THESE MINIMUM DIMENSIONS.
  
 16) INDICATE HOW THE GARAGE/RECREATION ROOM STRUCTURE
 COMPLIES WITH R806.1 VENTILATION REQUIRED. ENCLOSED
 ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS
 ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF RAFTERS
 SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE SPACE BY
 VENTILATING OPENINGS PROTECTED AGAINST THE ENTRANCE OF
 RAIN. VENTILATING OPENINGS SHALL BE PROVIDED WITH
 CORROSION-RESISTANT WIRE MESH, WIT H 1 / 8 INCH (3.2
 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM OPENINGS.
  
 17) SHOW COMPLIANCE WITH R502.1.2 * DRAFTSTOPPING
 REQUIRED. WHEN THERE IS USABLE SPACE BOTH ABOVE AND
 BELOW THE CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY,
 DRAFTSTOPS SHALL BE INSTALLED SO THAT THE AREA OF THE
 CONCEALED SPACE DOES NOT EXCEED 100 SQUARE FEET.
 DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO
 APPROXIMATELY EQUAL AREAS.
 R502.1.2.1 MATERIALS. DRAFTSTOPPING MATERIALS SHALL NOT
 BE LESS THAN 1/2" GYPSUM BOARD, 3/8" WOOD STRUCTURAL
 PANELS, 3/8" TYPE 2-M-W PARTICLEBOARD OR OTHER APPROVED
 MATERIALS ADEQUATELY SUPPORTED.
  
 18) SECTION 1 ON 6.1 SHOWS A 1-1/2" WATERSTOP AT THE
 STEM WALL FOUNDATION. PLEASE CORRECT.
  
 19) SPECIFY THE FIREBLOCKING REQUIRED FOR THE CONCEALED
 SPACES BETWEEN THE STAIR STRINGERS AT THE TOP AND
 BOTTOM OF THE RUN PER R 602.1.1.2*.
  
 20) THE WALL AND CEILING INSULATION R VALUES SPECIFIED
 IN SECTION 1 ON 6.1 OF THE PLANS DO NOT MATCH THE
 ENERGY CALCULATION FORM. PLEASE CORRECT.
  
 21) THE ENERGY CALCS. SPECIFY R19 FOR THE BLOCK WALLS
 AND THE PLANS HAVE R4.2. PLEASE CORRECT.
  
 22) PROVIDE A WALL SECTION FOR THE GARAGE/REC. ROOM
 STRUCTURE.
  
 23)R903.4 ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF
 DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE
 ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL
 BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR
 PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY
 THE ROOF SLOPE AND CONTRIBUTING ROOF AREA. R903.4.1
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING .
  
 INDICATE LOCATIONS SIZES ETC. FOR GARAGE ROOF SCUPPERS
 AND OVERFLOWS.
  
 24)SHOW COMPLIANCE WITH R320.7* PROTECTION AGAINST
 TERMITES AND DECAY. CONDENSATE LINES AND ROOF
 DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT AWAY FROM
 THE STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND PIPING,
 TAIL EXTENSIONS OR SPLASH BLOCKS. GUTTERS WITH DOWN
 SPOUTS ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS
 THAN 6 INCHES HORIZONTAL PROJECTION EXCEPT FOR GABLE
 END RAKES OR ON A ROOF ABOVE ANOTHER ROOF.
  
 25)ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE
 WITH SECTION R803.2.3.1* OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL
 BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT
 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS
 SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130
 MPH OR GREATER DESIGNWIND SPEEDS IN ACCORDANCE WITH
 FIGURE R803.2.3.1. PLEASE REVISE ROOF SHEATHING NAILING
 SCHEDULE ON 4.1 AND NOTES ON SECTION 1 ON 6.1.
  
 26) THE TRUSS LAYOUTS ARE REQUIRED TO BE APPROVED IN
 WRITING BY THE DESIGNER OF RECORD FOR THE STRUCTURE.
  
 27) THE ROOF TRUSS DRAWINGS DIFFER FROM THE ROOF
 FRAMING PLAN ON 4.1 FOR THE AREA ABOVE BED ROOM #2.
  
 28)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 29) THE WRONG TEST REPORT WAS SUBMITTED FOR THE AMARR
 GARAGE DOORS. THE DESIGN PRESSURES DO NOT MATCH THE
 INSTALLATION DRAWINGS THAT WERE SUBMITTED. SEE FL# 7153
 ON THE STATE WEBSITE.
  
 30) SUBMIT PRODUCT APPROVALS FOR SINGLE AND DOUBLE
 FRENCH DOORS WITHOUT SIDELITES.
  
 31) SUBMIT PRODUCT APPROVALS FOR THE SOLID CORE SIDE
 SWING DOOR AT THE GARAGE.
  
 IN ORDER TO EXPEDITE PLAN REVIEW. PLEASE SUBMIT A
 RESPONSE LETTER STATING HOW THESE COMMENTS HAVE BEEN
 ADDRESSED.
  
 NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE RESPONSES
 TO THESE COMMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714