| Plan Review Notes For Permit 07020389 |
| Permit Number |
07020389 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-20 14:40:09 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) PLEASE PROVIDE RETURN AIR TO BEDROOMS, BALANCED | | | RETURN AIR MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | | ACHIEVE PROPER RETURN AIR BALANCE. | | | (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF | | | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND USING AN | | | UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE | | | PROPER RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|