Plan Review Notes For Permit 07020367
Permit Number 07020367
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-14 14:18:42DENIED BY BUILDING
  
 1)THE COVERSHEET FOR THE FIRESTONE MODIFIED ROOF
 SYSTEM IS INCORRECT. THE ONE FOR THE 2004 FBC IS FL
 6760.
  
 2) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE.
  
 3) SPECIFY WHICH ONE OF THE APPROVED SYSTEMS WILL BE
 INSTALLED. ALSO SPECIFY WHICH FASTENING OPTION AND
 MAXIMUM DESIGN PRESSURE WILL BE USED. CIRCLE THE
 APPROPRIATE ITEMS IN THE PRODUCT APPROVAL.
  
 4) IF ENHANCED FASTENING IS REQUIRED TO MEET THE HIGER
 UPLIFT PRESSURES OF THE PERIMETER AND CORNER AREAS,
 SUBMIT RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION
 NUMBER 7 ON PAGE 34. THE PRESSURES FOR THE PERIMETER IS
 -59.2 AND FOR THE CORNERS IS -89 FOR UP TO 30' IN
 EXPOSURE CATEGORY B.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  