| 2007-02-14 14:18:42 | DENIED BY BUILDING | | | | | | 1)THE COVERSHEET FOR THE FIRESTONE MODIFIED ROOF | | | SYSTEM IS INCORRECT. THE ONE FOR THE 2004 FBC IS FL | | | 6760. | | | | | | 2) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE. | | | | | | 3) SPECIFY WHICH ONE OF THE APPROVED SYSTEMS WILL BE | | | INSTALLED. ALSO SPECIFY WHICH FASTENING OPTION AND | | | MAXIMUM DESIGN PRESSURE WILL BE USED. CIRCLE THE | | | APPROPRIATE ITEMS IN THE PRODUCT APPROVAL. | | | | | | 4) IF ENHANCED FASTENING IS REQUIRED TO MEET THE HIGER | | | UPLIFT PRESSURES OF THE PERIMETER AND CORNER AREAS, | | | SUBMIT RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION | | | NUMBER 7 ON PAGE 34. THE PRESSURES FOR THE PERIMETER IS | | | -59.2 AND FOR THE CORNERS IS -89 FOR UP TO 30' IN | | | EXPOSURE CATEGORY B. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|