| 2007-04-26 10:17:44 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT TWO CLEAR AND LEGIBLE COPIES OF ALL PRODUCT |
| | APPROVALS. NOTE: THESE WILL BE COPIED INTO FILES FOR |
| | RECORD RETENTION. THEREFORE, THEY MUST BE CLEAR AND |
| | READABLE. |
| | |
| | 4)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. SEE THE FL. COVERSHEET FOR THE FIRESTONE ROOFING |
| | MATERIAL ATTACHED TO THIS REVIEW. |
| | |
| | 5)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. THE LETTER FROM THE |
| | DESIGNER OF RECORD DOES NOT INCLUDE ALL OF THE ITEMS |
| | REQUIRED TO HAVE PRODUCT APPROVALS SUBMITTED BY RULE |
| | 9B-72. |
| | |
| | 6) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK, THE |
| | OUTSWING EXTERIOR GARAGE DOOR, THE 8' X 7' OVERHEAD |
| | GARAGE DOOR, THE SIMPSON AND USP CONNECTORS AND THE |
| | SINGLE HUNG WINDOWS. |
| | |
| | 7) THE PRODUCT APPROVAL NOA SUBMITTED FOR THE PGT |
| | SGD-70, SLIDING GLASS DOOR, HAS PAGES OF THE NOA THAT |
| | ARE ILLEGIBLE. THE ENTIRE REPORT MUST BE LEGIBLE. |
| | |
| | 8)SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED |
| | IN THE NOA FOR THE FIRESTONE MODIFIED ROOF SYSTEM WILL |
| | BE INSTALLED. INDICATE THE FASTENING OPTION THAT WILL |
| | BE USED AND DESIGN PRESSURE FOR THE SELECTED ASSEMBLY. |
| | CIRCLE THE APPROPRIATE ITEMS ON THE NOA. THE REQUIRED |
| | UPLIFT PRESSURES ARE -59.2 FOR ROOF ZONE 2 AND -89.0 |
| | FOR ROOF ZONE 3. IF THE DESIGN PRESSURES ARE TOO LOW |
| | FOR THESE AREAS, SUBMIT RAS 117 CALCULATIONS PER |
| | GENERAL LIMITATION #7. SEE PAGE 34 OF THE NOA. |
| | |
| | 9) NO ENERGY CALCULATIONS WERE SUBMITTED. PLEASE SUBMIT |
| | THE 2004 FORMS # 600C-04 . THE OWNER/AGENT IS REQUIRED |
| | TO SIGN THE ENERGY CALC. FORM. SEE FBC CHAPTER 13. |
| | |
| | 10) AN EMERGENCY ESCAPE AND RESCUE OPENING TO THE |
| | EXTERIOR REQUIRED BY FBC R310 MUST BE PROVIDED AT THE |
| | EXISTING BEDROOM ADJACENT TO THE ADDITION WHICH HAS THE |
| | REAR WINDOWSTHAT ARE BEING ENCLOSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |