Plan Review Notes
Plan Review Notes For Permit 07020357
Permit Number 07020357
Review Stop B
Sequence Number 2
Notes
Date Text
2007-02-15 17:41:00DENIED BY BUILDING
  
 1) THE MAXIMUM DESIGN PRESSURE FOR THE SYSTEM ON PAGE
 38 IS 60 PSF, WHICH IS TOO LOW FOR THE CORNERS WHICH
 REQUIRE 89 PSF. THE LIMITATION NUMBER 7 ON PAGE 40 OF
 THE PRODUCT APPROVAL ALLOWS ENHANCED FASTENING TO
 INCREASE THE PRESSURE. HOWEVER, TO DO THIS THE
 LIMITATION REQUIRES THAT RAS 117 CALCULATIONS MUST BE
 DONE BY AN ARCHITECT, ENGINEER OR REGISTERED ROOFING
 CONSULTANT AS STATED IN THE FIRST REVIEW. SUBMIT THE
 SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 THE PRODUCT APPROVAL.
  
 2) THE VALUE OF THE JOB IS BASED ON COSTS FROM ICC OR
 MARSHALLS AND SWIFT ESTIMATING GUIDE. IT DOES NOT
 MATTER WHO THE JOB IS FOR. THE VALUE HAS BEEN ADJUSTED
 ACCORDINGLY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  