| Notes |
| Date |
Text |
| 2007-02-15 17:41:00 | DENIED BY BUILDING | | | | | | 1) THE MAXIMUM DESIGN PRESSURE FOR THE SYSTEM ON PAGE | | | 38 IS 60 PSF, WHICH IS TOO LOW FOR THE CORNERS WHICH | | | REQUIRE 89 PSF. THE LIMITATION NUMBER 7 ON PAGE 40 OF | | | THE PRODUCT APPROVAL ALLOWS ENHANCED FASTENING TO | | | INCREASE THE PRESSURE. HOWEVER, TO DO THIS THE | | | LIMITATION REQUIRES THAT RAS 117 CALCULATIONS MUST BE | | | DONE BY AN ARCHITECT, ENGINEER OR REGISTERED ROOFING | | | CONSULTANT AS STATED IN THE FIRST REVIEW. SUBMIT THE | | | SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY | | | THE PRODUCT APPROVAL. | | | | | | 2) THE VALUE OF THE JOB IS BASED ON COSTS FROM ICC OR | | | MARSHALLS AND SWIFT ESTIMATING GUIDE. IT DOES NOT | | | MATTER WHO THE JOB IS FOR. THE VALUE HAS BEEN ADJUSTED | | | ACCORDINGLY. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|