| Plan Review Notes For Permit 07020357 |
| Permit Number |
07020357 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-14 07:00:50 | DENIED BY BUILDING | | | | | | 1) THE SYSTEM THAT WAS SELECTED ON PAGE 5 OF THE | | | CERTAINTEED MODIFIED ROOFING NOA HAS A MAXIMUM DESIGN | | | PRESSURE OF -45 PSF WHICH IS TOO LOW FOR THE PERIMETER | | | AND CORNER AREAS. THE PERIMETER REQUIRES -59.2 PSF AND | | | CORNERS REQUIRE -89 PSF. THE SELECTED SYSTEM ALSO HAS | | | LIMITATION NUMBER 9, WHICH DOES NOT ALLOW THE DESIGN | | | PRESSURES TO BE INCREASED BY ENHANCED FASTENING. SEE | | | LIMITATIONS ON PAGE 40. | | | NOTE: OTHER SYSTEMS DO ALLOW FOR INCREASED DESIGN | | | PRESSURES BY ENHANCED FASTENING (SEE LIMITATION NUMBER | | | 7). HOWEVER, THIS REQUIRES RAS 117 CALCULATIONS THAT | | | HAVE BEEN DONE BY AN ARCHITECT, ENGINEER OR REGISTERED | | | ROOF CONSULTANT. | | | | | | 2) THE VALUE OF THE WORK IS TOO LOW. PLEASE CHANGE TO | | | ADEQUATE VALUE. | | | | | | PLEASE CIRCLE THE APPROPRIATE ITEMS IN INK, RATHER THAN | | | HIGHLIGHTING. THE HIGHLIGHTER DOES NOT SHOW UP WHEN | | | COPIED FOR RECORD KEEPING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|