2007-02-14 07:00:50DENIED BY BUILDING
  
 1) THE SYSTEM THAT WAS SELECTED ON PAGE 5 OF THE
 CERTAINTEED MODIFIED ROOFING NOA HAS A MAXIMUM DESIGN
 PRESSURE OF -45 PSF WHICH IS TOO LOW FOR THE PERIMETER
 AND CORNER AREAS. THE PERIMETER REQUIRES -59.2 PSF AND
 CORNERS REQUIRE -89 PSF. THE SELECTED SYSTEM ALSO HAS
 LIMITATION NUMBER 9, WHICH DOES NOT ALLOW THE DESIGN
 PRESSURES TO BE INCREASED BY ENHANCED FASTENING. SEE
 LIMITATIONS ON PAGE 40.
 NOTE: OTHER SYSTEMS DO ALLOW FOR INCREASED DESIGN
 PRESSURES BY ENHANCED FASTENING (SEE LIMITATION NUMBER
 7). HOWEVER, THIS REQUIRES RAS 117 CALCULATIONS THAT
 HAVE BEEN DONE BY AN ARCHITECT, ENGINEER OR REGISTERED
 ROOF CONSULTANT.
  
 2) THE VALUE OF THE WORK IS TOO LOW. PLEASE CHANGE TO
 ADEQUATE VALUE.
  
 PLEASE CIRCLE THE APPROPRIATE ITEMS IN INK, RATHER THAN
 HIGHLIGHTING. THE HIGHLIGHTER DOES NOT SHOW UP WHEN
 COPIED FOR RECORD KEEPING.
  