| 2007-03-01 16:41:53 | | | | DENIED/INCOMPLETE INFORMATION | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE A LOAD CALCULATION FOR THE | | | LOAD INTENDED TO BE SERVED. 215.5. | | | | | | 2} PROVIDE A PANEL SCHEDULE FOR THE | | | GENERATOR PANEL. 106.3.5.4 FBC AS | | | AMMENDED. | | | | | | THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|