Plan Review Notes
Plan Review Notes For Permit 07020349
Permit Number 07020349
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-01 15:13:58 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE BELOW REFERENCED ARTICLES CAN BE FOUND IN THE 2004
 FLORIDA BUILDING CODE, CHAPTER 13, AND ARE THE NEW
 STANDARDS (AS OF 10/1/05) FOR LIGHTING ENERGY
 ALLOWANCES.
  
 1} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING. STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.
  
 2} INDICATE COMPLIANCE WITH 13-415.2ABC.1, PERFORMANCE
 CALCULATION PROCEDURES. SUBMIT FORMS WITH 13-415.2B OR
 13-415.2.C.1 DENSITIES.
  
 3} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHAL & SWIFT,
 MEANS, ETC) PER 108.3 FBC AS AMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.