| Plan Review Notes For Permit 07020339 |
| Permit Number |
07020339 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-05-01 07:07:51 | -------------DENIED--------------- | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS COMMENTS FOR CONTINUITY. | | | | | | 1. OK | | | | | | 2. OK | | | | | | 3. NOT ALL DUCT DIRECTIONAL NOTES CORRECTED. | | | | | | 4. OK | | | | | | 5. OK | | | | | | 6. NOT ALL DUCT DIRECTIONAL NOTES CORRECTED. | | | | | | 7. OK | | | | | | 8. OK | | | | | | 9. OK | | | | | | 10. OK | | | | | | 11. REFRIGERANT PIPE DETAIL SHOWS CONDENSATE FROM | | | AUXILIARY DRAIN PAN BEING DISCHARGED THRU AUXILIARY | | | WATER HEATER LINE. WATER HEATER IS NOT SHOWN IN A/C | | | CLOSET ON PLUMBING PLANS. AUXILIARY DRAIN PAN FOR A/C | | | CONDENSATE SHOULD HAVE EITHER A FLOAT SWITCH OR A | | | SECONDARY DRAIN LINE PIPED TO A CONSPICUOUS LOCATION | | | PER FRC M1411.3.1. CONDENSATE OVERFLOW CAN NOT BE | | | DISCHARGED INTO AN AUXILIARY WATER HEATER LINE AS IT | | | WILL NOT PROVIDE WARNING OF A PROBLEM WITH THE PRIMARY | | | CONDENSATE DRAIN. | | | | | | 12. OK | | | | | | 13. DRYER EXHAUST TERMINATION AT ROOF REQUIRES | | | BACKDRAFT DAMPER PER FRC M1501.1. | | | | | | 14. OK | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|