| 2007-04-15 15:59:54 | ********* UNSAT 2ND REVIEW *********** |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | CODES REQUIRED TO BE STATED ON PLANS FOR PROJECT. THESE |
| | WERE ADDED TO ELECTRICAL SHEETS; HOWEVER CODES COULD |
| | NOT BE LOCATED ON ARCHITECTURAL SHEETS. |
| | FBC 106.1.2 |
| | FBC 2004 W/2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE BE SURE THE TITLE BLOCKS FOR THE |
| | ARCHITECTURE FIRM AS LICENSED THROUGH THE STATE |
| | CONTAINS THE PRINTED FIRM CERTIFICATE OF AUTHORIZATION |
| | NUMBER ON ALL SHEETS WHICH CONTAIN THE FIRM. |
| | ON ANY SHEETS WHICH DO NOT NEED TO BE REPLACED, THIS |
| | MAY BE HAND PRINTED OR STAMPED ON SHEETS. |
| | FAC 61G1-16.004, FS481.219 *SEE ATTACHED PRINT OUT FROM |
| | THE STATE OF FLORIDA. |
| | |
| | 3) NOTE: PLEASE SEE THE MINIMUM CLEARANCES FOR THE A/C |
| | CU DISCONNECTS DOES NOT MEET 110.26 |
| | |
| | 4) NOTE: PLEASE SEE 422.13 AS THE LOADS FOR THE WATER |
| | HEATER MUST BE FIGURED INTO LOAD CALCULATIONS AT 125%. |
| | |
| | 6) NOTE: PLEASE SEE THE NEW SERVICE AS SHOWN MUST HAVE |
| | THE GROUNDING ELECTRODE CONDUCTOR CONTINUOUS TO FOOTER |
| | STEEL WITH ALL ITEMS AS SHOWN ON GROUNDING RISER PER |
| | 250.66 |
| | SHOWS #4, WHEN THIS SHOULD BE THE #2. 250.64C |
| | 250.66C IS USED WHEN THE SOLE CONNECTION. |
| | PLEASE CLARIFY ANY METALLIC COLD WATER PIPE ? |
| | |
| | 7) NOTE: PLEASE SEE CODE SECTIONS FOR LOAD CALCULATIONS |
| | FOR EACH ARE FROM THE 2002 NEC. |
| | PLEASE ADJUST TO THE 2005 NEC. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |