| 2007-03-15 10:20:48 | --------------DENIED---------------- |
| | |
| | FBC 2004 W/ 2006 REVISIONS |
| | FRC 2004 |
| | FBC,M 2004 |
| | |
| | 1. BUILDING PLAN SHOWS A UNIT A AND A UNIT B, AC PLAN |
| | SHOWS BOTH TO BE UNIT A. FOR PURPOSE OF CLARITY, PLEASE |
| | CORRELATE DRAWINGS. FBC 106.1.1 |
| | |
| | 2. PG AC-2 1ST FLOOR: PLEASE INDICATE THE SIZE OF THE |
| | DUCT BETWEEN THE 16X6 TRANSFER GRILLS. FBC 106.1.1 |
| | |
| | 3. PG AC-2 1ST FLOOR: LEFT UNIT SHOWS 10X6 DUCT DOWN TO |
| | 1ST FLOOR. THIS DUCT IS ALREADY ON THE FIRST FLOOR. |
| | SHOULD IT SAY ?UP TO 2ND FLOOR?? FBC 106.1.1 |
| | |
| | 4. PG AC-2 PIPING IN OR BENEATH CONCRETE FLOORS SHALL |
| | BE ENCASED IN A PIPE DUCT PER FRC R101.2, FBC,M |
| | 1107.2.1. |
| | |
| | 5. PG AC-2 1ST FLOOR: RIGHT UNIT SHOWS A 10X6 DUCT UP |
| | TO 1ST FLOOR. SHOULD THIS SAY ?UP TO 2ND FLOOR?? ALSO, |
| | PLEASE SHOW SIZE OF DIFFUSER AND CFM AT 4? ROUND FLEX |
| | DUCT TERMINATIONS. PLEASE CLARIFY. FBC 106.1.1 |
| | |
| | 6. PG AC-2 2ND FLOOR: LEFT UNIT SHOWS 22X8 DUCT UP TO |
| | 2ND FLOOR. DUCT IS ALREADY ON 2ND FLOOR. SHOULD IT SAY |
| | ?UP TO 3RD FLOOR?? ALSO, REFRIGERANT LINES ARE SHOWN |
| | GOING UP WHERE THEY SHOULD BE GOING DOWN AS WELL AS |
| | GOING DOWN WHERE THEY SHOULD BE GOING UP. PLEASE |
| | CLARIFY. FBC 106.1.1 |
| | |
| | 7. PG AC-2 2ND FLOOR: RIGHT UNIT FE-1 EXHAUST DUCT IS |
| | SHOWN GOING OUT SOUTH EXTERIOR WALL WITH NO WALL CAP. |
| | THERE IS ALSO A 4? ROUND DUCT GOING UP TO THE 3RD FLOOR |
| | FROM NOWHERE. PLEASE CLARIFY. FBC 106.1.1 |
| | |
| | 8. PGS AC-2 AND AC-3: PLEASE REMOVE CLOUDS FROM DRAWING |
| | FOR THE PURPOSE OF CLARITY AS THERE ARE YET TO BE ANY |
| | REVISIONS. |
| | |
| | 9. PG AC-3: DOOR SCHEDULE INDICATES LOUVERED DOORS ON |
| | A/C CLOSET. A SOLID DOOR W/ GASKET SHOULD BE USED AS |
| | THIS CLOSET IS BEING USED AS A PLENUM AND THE DRAWING |
| | OF RETURN AIR FROM A CLOSET IS PROHIBITED UNDER FRC |
| | M1602.2(5) |
| | |
| | 10. PG AC-3 EF-1 IN BOTH ROOMS LABELED ?BATH 2? THERE |
| | IS A 4? ROUND DUCT GOING TO A 5? ROUND ROOF CAP. IS |
| | THIS INTENTIONAL OR A MISTAKE? ALL OTHER ROOF CAPS |
| | MATCH THE CORRESPONDING DUCT SIZE. |
| | |
| | 11. PLEASE SHOW AN AUXILIARY OR SECONDARY DRAIN SYSTEM |
| | THAT IS IN COMPLIANCE WITH FRC 1411.3.1 |
| | |
| | 12. PLEASE INDICATE ON PLAN WHERE R-4.2 DUCT IS |
| | ACCEPTABLE AND WHERE R-6 DUCT IS REQUIRED. FBC 106.1.1 |
| | |
| | 13. PLEASE PROVIDE DETAIL ON PLAN SHOWING WHICH TYPES |
| | OF ROOF/WALL CAPS ARE TO BE USED AS THERE ARE DIFFERENT |
| | REQUIREMENTS FOR BATHROOM AND DRYER EXHAUST. SEE: FBC,M |
| | TABLE 401.6 AND FRC M1501.1 |
| | |
| | 14. GENERAL NOTE #15: THIS PROJECT IS UNDER FBC/FRC |
| | 2004 W/ 2006 REVISIONS, NOT FBC 2001. PLEASE CORRECT |
| | AND RESUBMIT. |
| | |
| | IF YOU HAVE ANY QUESTIONS REGARDING THIS REVIEW, PLEASE |
| | FEEL FREE TO CONTACT ME AT ANY TIME. |
| | |