| 2007-03-12 08:13:26 | DENIED |
| | REFERENCE: FBC-2004 W/2006 AMENDMENTS |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. PLEASE INDICATE CODE REFERENCES ON PLANS. SECTIONS |
| | 106.1.1 & 106.1.2. |
| | |
| | 2. SHT 2 OF 6A INDICATES 3" DUAL RPZV BACKFLOW |
| | PREVENTERS ON 4" DIP WATER LINE. PER TABLE 603.1(D), |
| | ALL BACKFLOW ASSEMBLIES SHALL BE AT LEAST THE SAME SIZE |
| | AS THE LINE IN WHICH THEY ARE INSTALLED.4" DUAL RPZV |
| | BACKFLOWS ARE REQUIRED. |
| | |
| | 3. SHTS A103 & P-3.SHT A103 SHOWS NO EMERGENCY |
| | OVERFLOW SCUPPER FOR AREA #4 OF THE ROOF, BUT SHT P-3 |
| | INDICATES AN OVERFLOW SCUPPER. PLEASE CORRELATE |
| | INFORMATION ON THESE TWO SHEETS. SECTION 106.1.1. |
| | |
| | 5. SHT P-5 WATER RISER DIAGRAMS DO NOT REFLECT THE |
| | FLOOR PLAN FOR THE REF. & THE WATER SERVICE ROUTING FOR |
| | BOTH UNITS. PLEASE CORRELATE. SECTION 106.1.1.- WATER |
| | RISER DIAGRAM FOR UNIT "B' DOES NOT REFLECT THE FLOOR |
| | PLAN AT THE 3RD FLOOR MASTER BATH AND BATH #2. OVERHEAD |
| | PIPING ON THE FLOOR PLAN IS SHOWN TO THE RIGHT OF THE |
| | W/CAND TUB, AND NO SHOWER IS INDICATED ON THE FLOOR |
| | PLAN. PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 6. SUBMIT A HORIZONTAL STORM RISER ISOMETRIC RISER, AND |
| | VERTICAL STORM RISER DIAGRAMS. SHOW ALL PIPE SIZES, AND |
| | INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE |
| | SYSTEM. SECTION 106.3.5.1.3(7)(13) & TABLE 1106.3. |
| | |
| | 7. SHT IR-1 IRRIGATION PLANS ARE INCOMPLETE. SHOW ALL |
| | PIPING AND INDICATE PIPE SIZE. SHOW THE LOCATION OF THE |
| | METER, BACKFLOW PREVENTER, & RAIN SENSOR. SECTION |
| | 106.1.1. |
| | |