| Date |
Text |
| 2007-03-02 16:47:32 | *** UNSAT ** |
| | |
| | 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGE SIN THE FBC WHICH WILL |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE ALSO SEE ELECTRICAL CHANGES UNDER THE 2005 |
| | INCLUDING ANY SECTIONS OF CODES WHICH ARE REFLECTED ON |
| | PLANS FROM THE PREVIOUS 2002 NEC. |
| | PLEASE LIST THE FOLLOWING FOR THIS REVIEWER AT A |
| | MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION AND |
| | OTHER INFORMATION ON TITLE BLOCKS FOR LANDSCAPE |
| | SHEETS. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND |
| | FS 481.219 |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADE(S). |
| | |
| | 3) NOTE: PLEASE SEE PLANS APPEAR TO SHOW A *D* FOR WHAT |
| | IS BEING ASSUMED AS A SMOKE DETECTOR. PLEASE KNOW THAT |
| | AS THE SYMBOL LEGEND DOES NOT CORRELATE WITH PLANS IT |
| | CAN NOT BE CONFIRMED AT THIS TIME. |
| | PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| | SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| | INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| | ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| | THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| | OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| | ALARMS. |
| | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY |
| | THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 4) NOTE: PLEASE KNOW THATTHE PLANS NEED TO LABEL AND |
| | PROVIDE ROOM AND ARE DESIGNATIONS ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS |
| | AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR |
| | EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN FROM |
| | COMMENTARY IN THE CODE WHICH STATES THE USE OF *GEN LT* |
| | ETC IS NOT ACCEPTABLE. |
| | |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 5) NOTE: PLEASE LABEL DEVICES WHICH ARE SHOWN OUTSIDE |
| | AS TO WHICH PANEL THEY ARE BEING FED FROM. PLEASE SEE |
| | THAT THE OUTSIDE GFI IS BEING SHOWN BY BOTH CONDENSING |
| | UNITS YET ONE GFI MAY NOT BE USED TO SERVICE OTHER |
| | OWNERS UNIT UNLESS A HOUSE PANEL IS PROVIDED? PLEASE |
| | ALSO SEE NOTE FOR SERVICE AS METER/MAIN COMBO PANELS |
| | ARE BEING SHOWN YET THE CU'S ARE BEING FED FROM PANELS |
| | INSIDE. |
| | 210.25 |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 6) NOTE: PLEASE SEE THAT THIS IS CONSIDERED ONE |
| | BUILDING AND ONLY ONE ELECTRICAL SERVICE IS PERMITTED. |
| | 230.2 |
| | PLEASE REVISE SERVICE RISER WHICH MAY INCLUDE TWO |
| | METERS FOR THE MULTI-FAMILY BUILDING. |
| | PLEASE KNOW ONE THE RISER IS REVISED, REVIEW OF NEW |
| | RISER WILL TAKE PLACE. |
| | |
| | 7) NOTE: PLEASE SEE THAT THE GROUNDING ELECTRODE DETAIL |
| | DOES NOT CARRY THE GROUNDING ELECTRODE CONDUCTOR TO THE |
| | REQUIRED FOOTER STEEL BEING LOCATED IN THE BOTTOM OF |
| | THE FOOTER AS REQUIRED PER 250.50,250.52. |
| | PLEASE SEE ONE NOTE MENTIONS SLAB, ONE SHOWS WALL |
| | CONNECTION? PLEASE ADJUST RISER FOR THIS. |
| | |
| | 8) NOTE: PLEASE SEE 210.52C1-5. |
| | PLEASE SEE UNIT A AS THE COUNTER SPACE GFI DOES NOT |
| | SEEM TO SERVE COUNTER FOR WHAT SEEMS TO BE SHOWN AS A |
| | PENINSULAR. |
| | PLEASE ALSO SEE THAT THE GFI AS SHOWN APPEARS TO BE |
| | LOCATED ON THE WALL WHICH IS IN THE DINING AREA. PLEASE |
| | ALSO SEE 210.52 AND SEE OTHER UNIT AND GO OVER COUNTER |
| | SPACE DEVICES AS ONE OR TWO APPEAR TO BE NEEDED. |
| | |
| | 9) NOTE: PLEASE BE SURE ALL SYMBOLS ON PLANS CORRELATE |
| | WITH THE SYMBOL LEGEND. PLEASE SEE SOME ITEMS ON PLANS |
| | WHICH ARE NOT LISTED. |
| | FBC 106.1.2, 106.3.5.4. |
| | |
| | 10) NOTE: PLEASE SEE NOTES FORM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS AND SHEETS. |
| | PLEASE SEE NOTES FROM ADDRESSING REVIEWER WHICH MAY |
| | AFFECT THE TITLE BLOCKS FOR ADDRESSING OF PROJECT. |
| | |
| | 11) NOTE: PLEASE SEE THE ELEVATION OF THE ELECTRICAL |
| | SERVICE EQUIPMENT AND MECHANICAL EQUIPMENT OUTSIDE MUST |
| | BE ABOVE THE BFE. |
| | PLEASE PROVIDE ELEVATION DETAIL. |
| | |
| | 12) NOTE: PLEASE SEE FBC 2004 13-606.1.ABC.1.2.4 FOR |
| | ANY RECESSED LIGHTING. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |