| 2007-06-15 14:30:09 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET A1 PLEASE CLEARLY INDICATE IF THE PROPOSED |
| | TANKLESS WATER HEATER IS GAS OR ELECTRIC ON THE |
| | RESUBMITTAL. |
| | |
| | 2. SHEET A2 PLUMBING RISER: PLEASE CORRECT THE |
| | FOLLOWING ON THE SANITARY ISOMETRIC PLUMBING RISER |
| | DIAGRAM. |
| | A} PLEASE CORRECT THE LOCATION OF THE TRAP AND |
| | STANDPIPE FOR THE WASHING MACHINE TO BE BELOW THE |
| | CLEANOUT 4' A.F.F. |
| | B} PLEASE DELETE THE 4" CLEANOUT BETWEEN THE |
| | PROPOSED TUB AND LAVS. |
| | C} PLEASE INDENTIFY THE CLEANOUT AT THE JUNCTION |
| | OF THE BUILDING SEWER AND BUILDING DRAIN AS A TWO-WAY |
| | CLEANOUT, PER FBC-2004 PLUMBING, SECTION 708.3.5. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS REVIEWER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |