| Plan Review Notes For Permit 07020324 |
| Permit Number |
07020324 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-06-18 08:49:23 | *** DENIED *** | | | 1) INFORMATION ON PLANS MAY NOT BE DONE IN PEN, AS | | | PLANS MAY BE ALTERED AFTER THE FACT. | | | | | | 2) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS. | | | | | | 3) ENERGY CALCULATIONS LINE 11 (A) ARE SHOWING THE | | | SUPPLY AIR DUCTS IN A CONDITIONED SPACE AS THE SUPPLY | | | DUCTS ARE IN THE ATTIC THAT WOULD BE AN UNCONDITIONED | | | SPACE, PLEASE CORRECT ENERGY CALCULATIONS. | | | | | | 4) COOLING LOAD CALCULATIONS (MANUAL J) ARE SHOWING THE | | | CEILING HEIGHT AT 10 FT. THE PLANS PAGE A-4 SHOW THE | | | CEILING HEIGHT AT 8 FT. PLEASE RE-CALCULATE THE COOLING | | | LOAD CALCULATIONS AT 8 FT.. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|