2007-06-18 08:49:23*** DENIED ***
 1) INFORMATION ON PLANS MAY NOT BE DONE IN PEN, AS
 PLANS MAY BE ALTERED AFTER THE FACT.
  
 2) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS.
  
 3) ENERGY CALCULATIONS LINE 11 (A) ARE SHOWING THE
 SUPPLY AIR DUCTS IN A CONDITIONED SPACE AS THE SUPPLY
 DUCTS ARE IN THE ATTIC THAT WOULD BE AN UNCONDITIONED
 SPACE, PLEASE CORRECT ENERGY CALCULATIONS.
  
 4) COOLING LOAD CALCULATIONS (MANUAL J) ARE SHOWING THE
 CEILING HEIGHT AT 10 FT. THE PLANS PAGE A-4 SHOW THE
 CEILING HEIGHT AT 8 FT. PLEASE RE-CALCULATE THE COOLING
 LOAD CALCULATIONS AT 8 FT..
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.