2007-06-06 07:29:20 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE LOAD CALCULATIONS SHOULD BE PER 220.83(B) SINCE
 A/C SYSTEM IS BEING ADDED.
  
 2} THE HEAT LOAD IN THE PANEL SCHEDULE DOES NOT
 CORRELATE WITH THE LOAD OF 8000W ON THE MECHANICAL
 SHEET.
  
 3} THE TANKLESS WATER HEATER SHOWN ON THE PLAN IS NOT
 ON THE SCHEDULE OR IN THE LOAD CALCULATIONS.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 5} BATH CIRCUIT IS REQUIRED , LOCATED PER 210.52(D),
 AND BE GFI PROTECTED PER 210.8(A) (1), FOR THE EXISTING
 BATH. EXISTING BUILDING CODE, SECTION 608.1.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS.
  