| Plan Review Notes For Permit 07020324 |
| Permit Number |
07020324 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-06-06 07:29:20 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE LOAD CALCULATIONS SHOULD BE PER 220.83(B) SINCE | | | A/C SYSTEM IS BEING ADDED. | | | | | | 2} THE HEAT LOAD IN THE PANEL SCHEDULE DOES NOT | | | CORRELATE WITH THE LOAD OF 8000W ON THE MECHANICAL | | | SHEET. | | | | | | 3} THE TANKLESS WATER HEATER SHOWN ON THE PLAN IS NOT | | | ON THE SCHEDULE OR IN THE LOAD CALCULATIONS. | | | | | | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. | | | | | | 5} BATH CIRCUIT IS REQUIRED , LOCATED PER 210.52(D), | | | AND BE GFI PROTECTED PER 210.8(A) (1), FOR THE EXISTING | | | BATH. EXISTING BUILDING CODE, SECTION 608.1. | | | | | | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH | | | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM | | | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|