Plan Review Notes
Plan Review Notes For Permit 07020324
Permit Number 07020324
Review Stop B
Sequence Number 3
Notes
Date Text
2007-06-19 13:18:13BUILDING REVIEW 3RD CHECKLIST:
 1- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS IF
 WORK IS NOT STARTED. NEED TO RE-RECORD NOTICE OF
 COMMENCEMENT.
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) PRECAST LINTELS.NOA 03-0605.05 SUBMITTED
 EXPIRED ON 05/21/06. NEED CURRENT ONE.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 PRODUCT APPROVALS HAVE AN APPROVED AND REVIEWED STAMP
 BUT IT LACKS THE MOST IMPORTANT INFORMATION. WHO
 REVIEWED AND APPROVED IT?.NEED TO PROVIDE THE NAME
 OF THE ENGINEER WHO REVIEWED AND APPROVED THE PRODUCT
 APPROVALS.
 ALSO,ENGINEER SIGNATUREIS NOT THESAME AS SHOWN ON
 FLOOR PLANS.
  
 4- HURRICANE SHUTTERS:
 A) PROVIDE COMPLETE AND CORRECT INSTALLATION
 SCHEDULE. INFORMATION SUBMITTED IS INCORRECT.USE
 CLEAN COPY. SEE ATTACHED CLEAN COPY. TRACO SECURITY
 WINDOWS IS NOT THE PRODUCT APPROVAL MANUFACTURER.
 COORDINATE SIZE OF OPENINGS AND DESIGN PRESSURES WITH
 FLOOR PLANS. REVISE SIZE TYPE AND SPACING OF ANCHORS.
 PROVIDE INFORMATION FOR TOP AND BOTTOM ANCHORS. WHAT'S
 #5 SHOWN ON CENTER BOLTS OR REINFORCING BARS COLUMN?.
  
 SEE ENGINEERED DRAWINGS FOR STORM SHUTTERS AND MARK
 SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNT) AND
 SPECIFIC TYPE OF ANCHOR AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES, PANEL SPAN,EDGE
 DISTANCE, CONNECTION TYPE AND STRUCTURE TO BE ATTACHED
 TO ( CONCRETE BLOCK).SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 5- ENGINEER TO PROVIDE ACTUAL CALCULATIONS FOR OPENING
 DESIGN PRESSURES. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.DESIGN PRESSURES SHOWN ON OPENINGS ARE LOW
 COMPARED TO REVISED TABLE 1609.6.2.1(2) OF FBC 2004 AND
 ACTUAL OPENING LOCATION, END OR INTERIOR ZONE.
  
 6- ENGINEER TO SPECIFYALL LOADS INCLUDING ATTIC LIVE
 LOADS AS REQUIRED BY SEC. R301 AND TABLE R301.5 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 7- INFORMATION SUBMITTED FOR EMERGENCY EGRESS WINDOWS
 IS INCORRECT.SEC. R301 AND TABLE R301.5HAVE NOTHING
 TO DO WITH EMERGENCY EGRESS. REVISE AS REQUIRED. SEE
 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT CODE SECTION
 FOR EGRESS WINDOWS AND REVISE ALL INFORMATION AS
 REQUIRED.
 ALSO, NET CLEAR OPENING: 20".THIS IS NET CLEAR
 OPENING IN WHAT DIRECTION? WIDTH?.
  
 8-REVISE INFORMATION GIVEN ON WIND INFORMATION - 2004
 FBC.SEEFBC 2004 INCLUDING THE REVISIONSAND
 SPECIFY CORRECT SECTIONS OF THE CODE.
 PROVIDE COMPLETE AND CORRECT SPECIFICATIONS FOR SIZE OF
 REINFORCING STEEL ANGLE TO SUPPORT EXISTING TIE BEAM.
 SPECIFICATIONS SUBMITTED ARE INCOMPLETE.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 9- COORDINATE LIVE AND DEAD LOADS SHOWN ON WIND
 INFORMATION - 2004 FBC AND STRUCTURAL LOADS INFORMATION
 GIVEN ON THE SAME SHEET.INFORMATION SHOWN DOESN'T
 MATCH.
  
 10- ROOF SHEATHING INFORMATION SHOWN ON PLYWOOD
 SHEATHING FASTENER SCHEDULE AND TYPICAL EXTERIOR WALL
 SECTION DOESN'T MATCH. REVISE AS REQUIRED.SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT
 TYPE AND FASTENER SPACING FOR INTERIOR ZONES AND ZONE
 3.
  
 11- ENGINEER TO SEE ATTACHED COPY OF FLORIDA STATUTE
 553.80(2)(B) REGARDING PLAN REVIEW FEES FORDESIGN
 PROFESSIONAL DOCUMENTS AND CONTINUOUS FAILURES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712