Plan Review Notes
Plan Review Notes For Permit 07020324
Permit Number 07020324
Review Stop M
Sequence Number 2
Notes
Date Text
2007-05-07 09:34:09*** DENIED ***
 1) THE ENGINEER LUIS LOPEZ LICENSE EXPIRED 2-28-07,
 PLEASE CORRECT.
  
 2) SEE PLANS PAGE A-1 (A/C DUCT LAY-OUT). CHANGES MAY
 NOT BE MADE BY HAND TO SIGNED AND SEALED PLANS.
  
 3) THE DUCT LAY-OUT IS FOR THE EXISTING PART OF THE
 HOUSE, YOU ONLY NEED TO SHOW THIS IF THAT DUCT-WORK IS
 TO BE REPLACED.
  
 4) PLEASE SUBMIT A DUCT LAY-OUT FOR THE NEW ADDITION
 AND EQUIPMENT LISTING FOR THE NEW EQUIPMENT (A/C).
  
 5) NEED TO SUBMIT TWO COPY'S OF THE MECHANICAL (A/C)
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.