Plan Review Notes
Plan Review Notes For Permit 07020324
Permit Number 07020324
Review Stop E
Sequence Number 2
Notes
Date Text
2007-05-02 10:46:28 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PLAN INDICATES A METER AND MAIN DISCONNECT ON
 THE STRUCTURE, THE RISER ONLY INDICATES A MAIN ONLY.
 PLEASE CORRELATE TO SHOW ACTUAL CONDITIONS.
  
 2} THE TANKLESS WATER HEATER APPEARS IN THE LOAD
 CALCULATIONS AS 8500 VA AND ON THE PANEL SCHEDULE AS
 4500 VA, PLEASE CORRECT., INCLUDE CORRECT OCP AND
 CONDUCTOR SIZE.
  
 3} THE BATHROOM AND "OUTSIDE" GFI CIRCUITS ARE NOT
 REQUIRED IN THE LOAD CALCULATIONS AS THEY ARE INCLUDED
 IN THE GENERAL LIGHTING CALCULATION. SEE 220.14(J),
 2005 NEC.
  
 4} THE AHU LOAD IN THE CALCULATION AND ON THE SCHEDULE
 ARE NOT THE SAME, THEREFORE THE OCP AND WIRE SIZES ARE
 INCORRECT. 310.16 PLEASE CORRELATE.
  
 5} THE WASHER AND DRYER ON THE PLAN APPEAR TO BE A
 STACKED UNIT, BUT ARE ON SEPARATE CIRCUITS IN THE
 SCHEDULE. PLEASE CORRECT TO INTENDED CONDITIONS.
  
 6} THE LOAD CALCULATIONS ARE DUPLICATED IN THE PANEL
 SCHEDULE AND IN THE LOAD CALCULATION
 SCHEDULE/WORKSHEET. THE PANEL SCHEDULE INDICATES
 CONNECTED LOAD AND THE CALC SHEET THE DEMAND LOAD.
 THERE IS NO NEED TOCALCULATE THE CONNECTED LOAD IN
 THE PANEL SCHEDULE. THE CONNECTED LOAD SHOULD BE SHOWN
 FOR CONDUCTOR AND OCP SIZE ONLY. PLEASE KEEP THIS IN
 MIND FOR FUTURE PLANS AS WELL AS THIS RESUB. THE
 REFERENCE TO 220.30 IS INCORRECT. SEE ARTICLE 220 IN
 THE 2005 NEC, ADOPTED DECEMBER 8, 2006.
  
 7} THE BATH CIRCUIT PER 210.11(C)(3) IS REQUIRED IN THE
 SCHEDULE.
  
 8} BOTH BATH RECEPTACLES (MASTER) MUST BE GFI PER 210.8
 (A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718