Plan Review Notes
Plan Review Notes For Permit 07020324
Permit Number 07020324
Review Stop B
Sequence Number 2
Notes
Date Text
2007-05-09 10:52:58BUILDING REVIEW SECOND CHECKLIST:
 1- PROPERTY IS LOCATED ON FLOOD ZONE A9 (ELEVATION 13).
 MINIMUM FLOOR ELEVATION REQUIRED FOR FINISH FLOOR
 ELEVATION AND ANY EQUIPMENTIS 13'-6" AS REQUIRED BY
 CITY ORDINANCE.PLANS TO INDICATE THIS MINIMUM
 ELEVATION.
 ALSO,SINCE PROPERTY IS LOCATED IN A FLOOD ZONE AREA,
 THEOWNER IS REQUIRED TO PROVIDE AN ELEVATION
 CERTIFICATE.
  
 2- NOTICE OF COMMENCEMENT WAS RECORDED ON 2/13/07.
 NOTICE OF COMMENCEMENT EXPIRES AFTER 90 DAYS OF
 RECORDING IF WORK IS NOT STARTED.THEREFORE, MAY NEED
 TO PROVIDE RE-RECORDED NOTICE OF COMMENCEMENT.
  
 3- AFTER PLANS ARE REVISED, BRING TEHM TO PALM BEACH
 COUNTY TO PAY THE IMPACT FEES (2300 N. JOG RD.
 (561)233-5115).BRING BACK TO THIS OFFICESTAMPED
 PLANS AND COPY OF PAID RECEIPT IF ADDITIONAL FEES ARE
 DUE.
  
 4- ENGINEER NEEDS TO UPDATE HIS LICENSE WITH THE STATE
 PRIOR TO RESUBMITTAL OF PLANS TO THIS OFFICE.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) WINDOW MULLIONS.
  
 B) PRECAST LINTELS.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 OF CITY AMENDMENTS TO FBC
 2004.
 ***NOTE: INDICATE NAME OF ENGINEER APPROVING THE
 PRODUCT APPROVALS.INFORMATION WAS NOT PROVIDED ON
 APPROVED PRODUCT APPROVALS.
  
 7- HURRICANE SHUTTERS:
 A) PROVIDE COMPLETE APPROVED PRODUCT APPROVAL.
 INFORMATION SUBMITTED IS NOT AN APPROVED PRODUCT
 APPROVAL AS REQUIRED BY DCA.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITING PRODUCT APPROVAL.
  
 C) PROVIDE KEY PLAN AND CORRECT INSTALLATION
 SCHEDULE. CHECK OPENING SIZE AND LOCATION, DESIGN
 PRESSURES, ANCHOR SPECIFIED,SHUTTER GLASS SEPARATION,
 EDGE DISTANCE VS PANEL SPAN,ANCHOR SPACING TOP AND
 BOTTOM, CENTER BOLTS REINFORCING, ETC. SEE PRODUCT
 APPROVAL TO FIND CORRECT INFORMATION AND REVISE AS
 REQUIRED.
  
 8- ENGINEER TO REVISE DESIGN PRESSURES FOR DOOR AND
 WINDOW OPENINGS ACCORDING TO SIZE AND LOCATION. END OR
 INTERIOR.SEEREVISED TABLE 1609.6.2.1(2) OF 2004 FBC
 AND REVISE DESIGN PRESSURES AS REQUIRED.OTHERWISE,
 PROVIDE COMPLETE ENGINEERING CALCULATIONS SHOWING
 CALCULATED VALUES. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 9- OWES $654.54 FOR UPDATED BUILDING PERMIT VALUATION
 AND RADON FEES.
  
 10- SHEET A1:
 A) SPECIFY ALL DESIGN LOADSAS REQUIRED BY SEC.
 R301 AND TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE.
 INFORMATION SUBMITTED IS INCORRECT.
  
 B) REVISE EGRESS WINDOW NOTES:MIN. TOTAL AREA IS
 FOR MIN. TOTAL OPENING AREA, NOT GLASS AREA. REVISE AS
 REQUIRED.
  
 11- SHEET A2:
 A) DEMOLITION REAR KITCHEN DETAIL:
 * SPECIFY IF EXISTING BEAM IS A POURED TIE BEAM OR BOND
 BEAM.PROPOSED FLOOR PLAN CALLS FOR TIE BEAM, WHILE
 THIS DETAIL CALLS FORBOND BEAM. THERE IS A BIG
 DIFFERENCE BETWEEN BOTH. REVISE/CLARIFY AS REQUIRED.
  
 ** HOW IS THE BEAM REINFORCED TO SUPPORT THE ADDITIONAL
 ROOF LOAD CONSIDERING THAT EXISTING POURED CONCRETE
 COLUMN WILL BE REMOVED. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 *** OPENING DIMENSION SHOWN ON THIS DETAIL DOESN'T
 MATCH OPENING DIMENSION SHOWN ON PROPOSED FLOOR PLAN.
  
 12- SHEETA3:
 A) ROOF PLAN:
 * REVISE NUMBER AND TYPE OF FASTENER SPECIFIED FOR
 SIMPSON HETA20 ANCHOR. SEE CURRENT CATALOG AND REVISE
 AS REQUIRED. OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSIS FOR TYPE AND NUMBER OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE MANUFACTURER.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 ** CLARIFY WHAT'S UA= 1805. THERE IS NOT ABREVIATION
 LEGEND TO IDENTIFY THIS ABREVIATION.
  
 *** WHAT'S W/14-DX1 1/2?. REVISE AS REQUIRED.
  
 B) ROOF SHEATHING DETAIL:
 * REVISE ROOF SHEATHING SPECIFICATIONS FOR TYPE OF NAIL
 TO BE USED. SEE SEC. R803..2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODEFOR TYPE OF NAIL TO BE USED.
  
 ** PLYWOOD THICKNESS DOESN'T MATCH SPECS ON TYP. EXT.
 WALL SECTION. REVISE AS REQUIRED.
  
 *** SPECIFICATIONS FOR ROOF SHEATHING SHOWN ON ROOF
 SHEATHING DETAIL AND TYP. WALL SECTION DON'T MATCH.
 REVISE AS REQUIRED AND CLEARLY IDENTIFY END ZONES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved