| Date |
Text |
| 2007-05-09 10:52:58 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- PROPERTY IS LOCATED ON FLOOD ZONE A9 (ELEVATION 13). |
| | MINIMUM FLOOR ELEVATION REQUIRED FOR FINISH FLOOR |
| | ELEVATION AND ANY EQUIPMENTIS 13'-6" AS REQUIRED BY |
| | CITY ORDINANCE.PLANS TO INDICATE THIS MINIMUM |
| | ELEVATION. |
| | ALSO,SINCE PROPERTY IS LOCATED IN A FLOOD ZONE AREA, |
| | THEOWNER IS REQUIRED TO PROVIDE AN ELEVATION |
| | CERTIFICATE. |
| | |
| | 2- NOTICE OF COMMENCEMENT WAS RECORDED ON 2/13/07. |
| | NOTICE OF COMMENCEMENT EXPIRES AFTER 90 DAYS OF |
| | RECORDING IF WORK IS NOT STARTED.THEREFORE, MAY NEED |
| | TO PROVIDE RE-RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 3- AFTER PLANS ARE REVISED, BRING TEHM TO PALM BEACH |
| | COUNTY TO PAY THE IMPACT FEES (2300 N. JOG RD. |
| | (561)233-5115).BRING BACK TO THIS OFFICESTAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF ADDITIONAL FEES ARE |
| | DUE. |
| | |
| | 4- ENGINEER NEEDS TO UPDATE HIS LICENSE WITH THE STATE |
| | PRIOR TO RESUBMITTAL OF PLANS TO THIS OFFICE. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) WINDOW MULLIONS. |
| | |
| | B) PRECAST LINTELS. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 OF CITY AMENDMENTS TO FBC |
| | 2004. |
| | ***NOTE: INDICATE NAME OF ENGINEER APPROVING THE |
| | PRODUCT APPROVALS.INFORMATION WAS NOT PROVIDED ON |
| | APPROVED PRODUCT APPROVALS. |
| | |
| | 7- HURRICANE SHUTTERS: |
| | A) PROVIDE COMPLETE APPROVED PRODUCT APPROVAL. |
| | INFORMATION SUBMITTED IS NOT AN APPROVED PRODUCT |
| | APPROVAL AS REQUIRED BY DCA. |
| | |
| | B) ENGINEER OF RECORD TO REVIEW AND APPROVE IN |
| | WRITING PRODUCT APPROVAL. |
| | |
| | C) PROVIDE KEY PLAN AND CORRECT INSTALLATION |
| | SCHEDULE. CHECK OPENING SIZE AND LOCATION, DESIGN |
| | PRESSURES, ANCHOR SPECIFIED,SHUTTER GLASS SEPARATION, |
| | EDGE DISTANCE VS PANEL SPAN,ANCHOR SPACING TOP AND |
| | BOTTOM, CENTER BOLTS REINFORCING, ETC. SEE PRODUCT |
| | APPROVAL TO FIND CORRECT INFORMATION AND REVISE AS |
| | REQUIRED. |
| | |
| | 8- ENGINEER TO REVISE DESIGN PRESSURES FOR DOOR AND |
| | WINDOW OPENINGS ACCORDING TO SIZE AND LOCATION. END OR |
| | INTERIOR.SEEREVISED TABLE 1609.6.2.1(2) OF 2004 FBC |
| | AND REVISE DESIGN PRESSURES AS REQUIRED.OTHERWISE, |
| | PROVIDE COMPLETE ENGINEERING CALCULATIONS SHOWING |
| | CALCULATED VALUES. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 9- OWES $654.54 FOR UPDATED BUILDING PERMIT VALUATION |
| | AND RADON FEES. |
| | |
| | 10- SHEET A1: |
| | A) SPECIFY ALL DESIGN LOADSAS REQUIRED BY SEC. |
| | R301 AND TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | INFORMATION SUBMITTED IS INCORRECT. |
| | |
| | B) REVISE EGRESS WINDOW NOTES:MIN. TOTAL AREA IS |
| | FOR MIN. TOTAL OPENING AREA, NOT GLASS AREA. REVISE AS |
| | REQUIRED. |
| | |
| | 11- SHEET A2: |
| | A) DEMOLITION REAR KITCHEN DETAIL: |
| | * SPECIFY IF EXISTING BEAM IS A POURED TIE BEAM OR BOND |
| | BEAM.PROPOSED FLOOR PLAN CALLS FOR TIE BEAM, WHILE |
| | THIS DETAIL CALLS FORBOND BEAM. THERE IS A BIG |
| | DIFFERENCE BETWEEN BOTH. REVISE/CLARIFY AS REQUIRED. |
| | |
| | ** HOW IS THE BEAM REINFORCED TO SUPPORT THE ADDITIONAL |
| | ROOF LOAD CONSIDERING THAT EXISTING POURED CONCRETE |
| | COLUMN WILL BE REMOVED. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | *** OPENING DIMENSION SHOWN ON THIS DETAIL DOESN'T |
| | MATCH OPENING DIMENSION SHOWN ON PROPOSED FLOOR PLAN. |
| | |
| | 12- SHEETA3: |
| | A) ROOF PLAN: |
| | * REVISE NUMBER AND TYPE OF FASTENER SPECIFIED FOR |
| | SIMPSON HETA20 ANCHOR. SEE CURRENT CATALOG AND REVISE |
| | AS REQUIRED. OTHERWISE, PROVIDE COMPLETE ENGINEERING |
| | ANALYSIS FOR TYPE AND NUMBER OF FASTENERS THAT DIFFER |
| | FROM THOSE TESTED AND PUBLISHED BY THE MANUFACTURER. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | ** CLARIFY WHAT'S UA= 1805. THERE IS NOT ABREVIATION |
| | LEGEND TO IDENTIFY THIS ABREVIATION. |
| | |
| | *** WHAT'S W/14-DX1 1/2?. REVISE AS REQUIRED. |
| | |
| | B) ROOF SHEATHING DETAIL: |
| | * REVISE ROOF SHEATHING SPECIFICATIONS FOR TYPE OF NAIL |
| | TO BE USED. SEE SEC. R803..2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODEFOR TYPE OF NAIL TO BE USED. |
| | |
| | ** PLYWOOD THICKNESS DOESN'T MATCH SPECS ON TYP. EXT. |
| | WALL SECTION. REVISE AS REQUIRED. |
| | |
| | *** SPECIFICATIONS FOR ROOF SHEATHING SHOWN ON ROOF |
| | SHEATHING DETAIL AND TYP. WALL SECTION DON'T MATCH. |
| | REVISE AS REQUIRED AND CLEARLY IDENTIFY END ZONES. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| | |