2007-03-09 09:16:40DENIED
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE CODE COMPLIANCE:
  
 1. SHEET A2 ISOMETRIC SANITARY RISER DIAGRAM: THE
 SANITARY RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE REFERENCE THE ATTACHED SANITARY RISER DIAGRAM TO
 THE PLUMBING COMMENTS THAT REFLECTS THE FLOOR PLAN AND
 IS CODE COMPLIANT.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4(9)
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: NOT ALL PIPES ARE SIZED AND NOT ALL CLEANOUTS ARE
 LOCATED.
  
 3. THE FOLLOWING IS REQUIRED FOR THE WASHING MACHINE:
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING
 NOTE: PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE THREE INCH
 (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL.
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE LOCATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). PLEASE
 INDICATE THIS ON THE RESUBMITTAL.
  
 4. SHEET A4 ISOMETRIC SANITARY RISER DIAGRAM DOES NOT
 INDICATE THE FOLLOWING CLEANOUT. ITS HARD TO TELL ON
 THE RISER DIAGRAM WHERE THE SANITARY PIPING LEAVES THE
 BUILDING. IF THE WASHING MACHINE AND THE MASTER BATH
 BOTH EXIT THE BUILDING THEY WILL BOTH NEED TWO-WAY
 CLEANOUTS. PLEASE CLARIFY AND CORRECT ON THE
 RESUBMITTAL.
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
  
 5. SHEET A1 PLUMBING NOTES NUMBER 1: PLEASE DELETE "
 MINIMUM SLOPE SHALL BE 1/8" PER FOOT." AND ADD THE
 FOLLOWING IN ITS PLACE " SLOPE SHALL BE PER FBC-2004
 PLUMBING, TABLE 704.1."
  
 ******IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL. PLEASE REFERENCE THE ATTACHED CORRECTED
 ISOMETRIC SANITARY RISER DIAGRAM TO THE PLUMBING
 COMMENTS FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  