| 2007-02-27 09:33:40 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} INDICATE WHETHER THE SERVICE IS NEW OR EXISTING. |
| | NOTE: IF NEW OR RELOCATED THERE MAY BE ADDITIONAL |
| | COMMENTS REGARDING DISCONNECTING MEANS, OCP, GROUNDING |
| | AND AIC RATINGS PER 225, 230, 250 AND 110. |
| | |
| | 2}PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 3} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW |
| | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS." |
| | |
| | 4} A RECEPTACLE MUST BE ADDED IN THE MASTER BECROOM TO |
| | COMPLY WITH 210.52(A)(1). |
| | |
| | 5} THE RECEPTACLES IN THE BATHROOM MUST INDICATE |
| | COMPLIANCE WITH 210.8(A)(1) GFI PROTECTED. |
| | |
| | 6} A GFI RECEPTACLE MUST BE INSTALLED OUTSIDE IN THE |
| | BACK PER 210.52(E). |
| | |
| | 7} A RECEPTACLE MUST BE ADDED WITHIN 25' OF THE A/C |
| | CONDENSER, IF NONE EXISTS. |
| | |
| | 8} REFERENCES TO THE 2001 BUILDING CODE ARE INCORRECT |
| | AND MUST BE CHANGED TO 2004. THE REASON FOR THAT |
| | COMMENT IN AN ELECTRICAL REVIEW IS TO CLARIFY THAT THE |
| | 2005 NEC IS CURRENTLY ADOPTED, WHICH IS REFERENCED IN |
| | THE 2004 FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |