Plan Review Notes
Plan Review Notes For Permit 07020324
Permit Number 07020324
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-27 09:33:40 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} INDICATE WHETHER THE SERVICE IS NEW OR EXISTING.
 NOTE: IF NEW OR RELOCATED THERE MAY BE ADDITIONAL
 COMMENTS REGARDING DISCONNECTING MEANS, OCP, GROUNDING
 AND AIC RATINGS PER 225, 230, 250 AND 110.
  
 2}PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 3} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 4} A RECEPTACLE MUST BE ADDED IN THE MASTER BECROOM TO
 COMPLY WITH 210.52(A)(1).
  
 5} THE RECEPTACLES IN THE BATHROOM MUST INDICATE
 COMPLIANCE WITH 210.8(A)(1) GFI PROTECTED.
  
 6} A GFI RECEPTACLE MUST BE INSTALLED OUTSIDE IN THE
 BACK PER 210.52(E).
  
 7} A RECEPTACLE MUST BE ADDED WITHIN 25' OF THE A/C
 CONDENSER, IF NONE EXISTS.
  
 8} REFERENCES TO THE 2001 BUILDING CODE ARE INCORRECT
 AND MUST BE CHANGED TO 2004. THE REASON FOR THAT
 COMMENT IN AN ELECTRICAL REVIEW IS TO CLARIFY THAT THE
 2005 NEC IS CURRENTLY ADOPTED, WHICH IS REFERENCED IN
 THE 2004 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  
  
  
  