| 2007-03-28 17:50:30 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- PROVIDE 2 COPIES OF EVERYTHING. |
| | |
| | 2- PROVIDE NOC AS REQUIRED BY SEC. 713.13 FLORIDA |
| | STATUTE. |
| | |
| | 3- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| | COUNTY TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |
| | 4- ENGINEER TO CHECK WITH DBPR TO UPDATE HIS LICENSE |
| | STATUS. |
| | |
| | 5- ENGINEER'S SEAL IS NOT LEGIBLE. UNABLE TO DETERMINE |
| | IF USING UPDATED SEAL. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (TWO COPIES)AS REQUIRED |
| | BY RULE 9B-72 FOR: |
| | A) WINDOW MULLIONS. |
| | |
| | B) TRUSS CONNECTORS SPECIFIED ON PLANS AND DETAILS. |
| | |
| | 7- ENGINEER TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 8- HURRICANE SHUTTERS: |
| | A) PROVIDE PRODUCT APPROVAL (REVIEWED AND APPROVED |
| | BY THE ENGINEER). |
| | |
| | B) PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE OF INSTALLATION SCHEDULE. COMPLETE ALL |
| | THE INFORMATION. |
| | |
| | 9- PROVIDE CALCULATIONS FOR DESIGN PRESSURES AT DOORS |
| | AND WINDOWS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | THEY ARE TOO LOW COMPARED TOZONE LOCATION AND TABLE |
| | R301.2(2) OF 2004 FLORIDARESIDENTIAL CODE. |
| | |
| | 10- VALUE DECLARED ON THE PERMIT APPLICATION IS TOO |
| | LOW. IT WAS UPDATED TO $64,000 AS REQUIRED BY SEC. |
| | 108.3 CITY AMENDMENTS TO FBC 2004. THEREFORE, OWES |
| | $654.54FOR ADDITIONAL PERMIT FEES AND RADON FEES. |
| | |
| | 11- SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 12- SHEET A1: |
| | A) SPECIFY ALL DESIGN LOADS INCLUDING LIVE AND DEAD |
| | LOADS AS REQUIRED BY SEC. R301 AND TABLE R301.5 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. INFORMATION SUBMITTED IS |
| | INCOMPLETE AND NEED TO ADDRESS PROPER CODE. |
| | |
| | B) REVISE EMERGENCY EGRESS INFORMATION. SEE SEC. |
| | R310 OF 2004 FLORIDA RESIDENTIALCODE FOR PROPER CODE |
| | SECTIONS.. |
| | |
| | C) AREA CALCULATIONS DON'T ADD UP.REVISE AS |
| | REQUIRED. |
| | |
| | D) CLARIFY WHY SHOWING VERTICAL REINFORCEMENT |
| | COLUMNS ON EXISTING SLAB. THIS NEEDS TO BE SHOWN ON |
| | FOUNDATION PLAN. |
| | |
| | E) SEE REDLINED COMMENTS ON ALL PLANS AND RETURN |
| | REVIEWED SET AFTER ALL CORRECTIONS ARE DONE TO EXPEDITE |
| | REVIEW PROCESS. |
| | |
| | 13- SHEET A2: |
| | A) IF CLOSING EXISTING BATHROOM WINDOW, THEN NEED TO |
| | PROVIDE MECHANICAL VENTILATION. |
| | |
| | B) NEED TO PROVIDE COMPLETE DETAILS/ SECTIONS AND |
| | SPECS FOR NEW OPENING AT EXISTING BEARING WALL BY |
| | KITCHEN AREA. SPECIFY COLUMNS, BEAM, ETC. AND SHORING. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 14- SHEET A3: |
| | A) SPECIFY CALCULATED UPLIFT LOADS ON ROOF FRAMING |
| | PLAN TO VERIFY CONNECTORS COMPLIANCE. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | B) REVISE NUMBER AND TYPE OF FASTENER SPECIFIED FOR |
| | TRUSS CONNECTORS. SEE CURRENT CATALOG.SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | C) FASTENER SCHEDULE AND CALCULATIONS HAS NOTHING TO |
| | DO WITH ROOF PLAN SHOWN. REVISE/CLARIFY AS REQUIRED. |
| | PROVIDE ONLY THE INFORMATION THAT IS RELEVANT TO THIS |
| | PROJECT. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | D) INFORMATION ON BEAM SCHEDULE, LINTEL SCHEDULE, |
| | TYPICAL WALL SECTION AND TYP BEAM DETAIL A-A-4 TO |
| | MATCH. REVISE AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | E) REVISE PLYWOOD SHEATHING FASTENER SCHEDULE AND |
| | ROOF SHEATHING DETAIL AND TYPICAL WALL SECTION.SEE |
| | SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 15- SHEET A4: |
| | A) INFORMATION ON TYP. WALL SECTION REGARDING |
| | CONCRETE STRENGTH DOESN'TMATCH INFORMATION SHOWN ON |
| | FOUNDATION PLAN. REVISE AS REQUIRED. |
| | |
| | B) ROOF SHOWN ON ELEVATIONS DON'T MATCH ROOF FRAMING |
| | PLAN. REVISE AS REQUIRED. SEE AREA OF NEW ROOF MEETING |
| | EXISTING ROOF. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |