Plan Review Notes
Plan Review Notes For Permit 07020324
Permit Number 07020324
Review Stop B
Sequence Number 1
Notes
Date Text
2007-03-28 17:50:30BUILDING REVIEW CHECKLIST:
  
 1- PROVIDE 2 COPIES OF EVERYTHING.
  
 2- PROVIDE NOC AS REQUIRED BY SEC. 713.13 FLORIDA
 STATUTE.
  
 3- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 4- ENGINEER TO CHECK WITH DBPR TO UPDATE HIS LICENSE
 STATUS.
  
 5- ENGINEER'S SEAL IS NOT LEGIBLE. UNABLE TO DETERMINE
 IF USING UPDATED SEAL.
  
 6- PROVIDE PRODUCT APPROVAL (TWO COPIES)AS REQUIRED
 BY RULE 9B-72 FOR:
 A) WINDOW MULLIONS.
  
 B) TRUSS CONNECTORS SPECIFIED ON PLANS AND DETAILS.
  
 7- ENGINEER TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- HURRICANE SHUTTERS:
 A) PROVIDE PRODUCT APPROVAL (REVIEWED AND APPROVED
 BY THE ENGINEER).
  
 B) PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE OF INSTALLATION SCHEDULE. COMPLETE ALL
 THE INFORMATION.
  
 9- PROVIDE CALCULATIONS FOR DESIGN PRESSURES AT DOORS
 AND WINDOWS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 THEY ARE TOO LOW COMPARED TOZONE LOCATION AND TABLE
 R301.2(2) OF 2004 FLORIDARESIDENTIAL CODE.
  
 10- VALUE DECLARED ON THE PERMIT APPLICATION IS TOO
 LOW. IT WAS UPDATED TO $64,000 AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004. THEREFORE, OWES
 $654.54FOR ADDITIONAL PERMIT FEES AND RADON FEES.
  
 11- SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 12- SHEET A1:
 A) SPECIFY ALL DESIGN LOADS INCLUDING LIVE AND DEAD
 LOADS AS REQUIRED BY SEC. R301 AND TABLE R301.5 OF 2004
 FLORIDA RESIDENTIAL CODE. INFORMATION SUBMITTED IS
 INCOMPLETE AND NEED TO ADDRESS PROPER CODE.
  
 B) REVISE EMERGENCY EGRESS INFORMATION. SEE SEC.
 R310 OF 2004 FLORIDA RESIDENTIALCODE FOR PROPER CODE
 SECTIONS..
  
 C) AREA CALCULATIONS DON'T ADD UP.REVISE AS
 REQUIRED.
  
 D) CLARIFY WHY SHOWING VERTICAL REINFORCEMENT
 COLUMNS ON EXISTING SLAB. THIS NEEDS TO BE SHOWN ON
 FOUNDATION PLAN.
  
 E) SEE REDLINED COMMENTS ON ALL PLANS AND RETURN
 REVIEWED SET AFTER ALL CORRECTIONS ARE DONE TO EXPEDITE
 REVIEW PROCESS.
  
 13- SHEET A2:
 A) IF CLOSING EXISTING BATHROOM WINDOW, THEN NEED TO
 PROVIDE MECHANICAL VENTILATION.
  
 B) NEED TO PROVIDE COMPLETE DETAILS/ SECTIONS AND
 SPECS FOR NEW OPENING AT EXISTING BEARING WALL BY
 KITCHEN AREA. SPECIFY COLUMNS, BEAM, ETC. AND SHORING.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 14- SHEET A3:
 A) SPECIFY CALCULATED UPLIFT LOADS ON ROOF FRAMING
 PLAN TO VERIFY CONNECTORS COMPLIANCE. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) REVISE NUMBER AND TYPE OF FASTENER SPECIFIED FOR
 TRUSS CONNECTORS. SEE CURRENT CATALOG.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 C) FASTENER SCHEDULE AND CALCULATIONS HAS NOTHING TO
 DO WITH ROOF PLAN SHOWN. REVISE/CLARIFY AS REQUIRED.
 PROVIDE ONLY THE INFORMATION THAT IS RELEVANT TO THIS
 PROJECT. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 D) INFORMATION ON BEAM SCHEDULE, LINTEL SCHEDULE,
 TYPICAL WALL SECTION AND TYP BEAM DETAIL A-A-4 TO
 MATCH. REVISE AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 E) REVISE PLYWOOD SHEATHING FASTENER SCHEDULE AND
 ROOF SHEATHING DETAIL AND TYPICAL WALL SECTION.SEE
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 15- SHEET A4:
 A) INFORMATION ON TYP. WALL SECTION REGARDING
 CONCRETE STRENGTH DOESN'TMATCH INFORMATION SHOWN ON
 FOUNDATION PLAN. REVISE AS REQUIRED.
  
 B) ROOF SHOWN ON ELEVATIONS DON'T MATCH ROOF FRAMING
 PLAN. REVISE AS REQUIRED. SEE AREA OF NEW ROOF MEETING
 EXISTING ROOF.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712