Plan Review Notes
Plan Review Notes For Permit 07020316
Permit Number 07020316
Review Stop B
Sequence Number 2
Notes
Date Text
2007-04-12 12:46:00BUILDING PLAN REVIEW
 PERMIT:07020316
 ADD: 250 S. AUSTRALIAN AVE #300
 CONT:ITASCA CONST.
 TEL: (561)241-4999
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE APPLICATION STATES THE WORK WILL CARRIED OUT ON
 THE 3RD FLOOR ONLY,HOWEVER, THE DRAWINGS SHOW WORK ON
 THE 2ND AND 3RD FLOORS. EITHER REMOVE THE INFORMATION
 REGARDING THE SECOND FLOOR FROM THE PACKAGE OR INCLUDE
 IT ON THE APPLICATION. IF THIS APPLICATION IS FOR
 DEMOLITION ONLY, THEN, ONLY THE DEMOLITION DRAWINGS
 SHALL BE SUBMITTED AT THIS TIME. REMOVE ALL OTHER
 DRAWINGS FROM THE PACKAGE.
 PARTIALLY
 ADDRESSED.*********************************************
 *********************
  
 3)106.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICAATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THE CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5)
  
 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. IF IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATEDON THE APPLICATION, THE PERMIT
 SHALL BE DENIED. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALLBE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE.OUR VALUATION REFERENCE IS
 ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES PER 108.3 FBC*
 NOT
 ADDRESSED**********************************************
 *****************
  
 5)FBC 2004 (EXISTING) INDICATE THE LEVEL OF
 ALTERATION. SEE CH. 3. FOR MORE INFORMATION.
 NOT
 ADDRESSED**********************************************
 *******************
  
 6)THE APPLICATION IS FOR THE DEMOLITION ONLY. REMOVE
 ALL OTHER DRAWINGS WHICH DOES NOT PERTAIN TO THE
 DEMOLITION OF THE PROJECT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726