Plan Review Notes
Plan Review Notes For Permit 07020305
Permit Number 07020305
Review Stop P
Sequence Number 2
Notes
Date Text
2007-06-06 09:01:41DENIED;
 1. PAGE P-1 DRINKING FOUNTAIN NOT SHOW ON EQUIPMENT
 SCHEDULE, FLOOR PLAN OR RISER DIAGRAMS ( WATER OR
 SANITARY).
 2.FLOOR SINK NOT VENTED.
 3.SHUTOFF VALVE REQUIRED FOR TENANT WATER SERVICE. (
 SHOW ON WATER RISER DIAGRAM)
 4. WATER HEATER, FLOOR SINK, AND GLASS WASHER ARE NOT
 SHOWN ON FLOOR PLAN, PAGE A-3.
 PLUMBING PLAN REVIEW BY;